An MCCB (moulded case circuit breaker) protects feeders and incomers beyond an MCB's range, typically 16 A to 1600 A. It is the main breaker of distribution panels, motor control centres and generator incomers.
Most asked for: 3 pole and 4 pole MCCB, 100 A, 250 A, 400 A and 630 A, thermal magnetic release, electronic (microprocessor) release, 25 kA to 70 kA breaking capacity.
Use an MCCB when the current is above about 100 A, when the fault level at the board is higher than an MCB's 10 kA, or when you need an adjustable overload setting. Below that, an MCB is smaller and cheaper.
A thermal magnetic release is simple and economical, with an overload setting adjustable over a limited range. An electronic release (LSI or LSIG) lets you set long time, short time, instantaneous and earth fault protection precisely, which matters for discrimination between upstream and downstream breakers.
Icu is the ultimate breaking capacity: the largest fault the MCCB can clear once. Ics is the service breaking capacity: the fault level it can clear and stay in service. Choose Icu above the fault level at the board, and prefer Ics equal to 100% of Icu for incomers.