A power contactor switches a motor or other heavy load on and off from a low power control signal. It is the working switch of every motor starter and pump panel, rated by its current in AC-3 (motor) duty.
Most asked for: 3 pole contactor, 9 A to 95 A AC-3, 230 V AC, 415 V AC and 24 V DC coil, contactor with auxiliary contacts, 4 pole contactor for AC-1 loads.
Take the motor's full load current and choose a contactor whose AC-3 rating is equal or higher. For a 415 V three phase motor the full load current is roughly 2 A per kW (about 1.5 A per HP). For star-delta starters the main and delta contactors carry 58% of the line current and the star contactor 33%.
AC-1 is the rating for resistive loads such as heaters and lighting. AC-3 is the rating for starting and stopping squirrel cage motors, and is lower for the same contactor. Size motors on AC-3.
The coil voltage must match the control circuit, not the motor: commonly 230 V AC or 415 V AC from the mains, 110 V AC from a control transformer, or 24 V DC from a PLC panel.