This device is a rated current 40A circuit breaker from EasyPact CVS250N. The rated breaking capacity(Ics) is 50kA at 415VAC,and complete range with Ics=100%Icu. The version of breaker is 3poles frame with detection on 3poles, also accompanied TM-D trip unit for thermal-magnetic protection. It is conformed to standard IEC60947-2 for circuit breakers part. This device is certified for operation in pollution degree III environment as defined IEC60947-1& IEC60664-1, and respected for RoHs requirement as european environment directive EC/2002/95. It can be mounted by blackplate or Din rail,also through the door of class II switchboard without downgrading switchboard insulation. The front of toggle offers IP40 protection, but when it is equiped extended rotary handle inside the switchboard, additional IP54 protection degree for extended rotary handle. This series have slots for electrical auxiliaries(MN/MX/OF/SD),depending on the type of trip unit if rotary handle installed. The fixed dimension is 140mm width.255mm height,110mm depth,
MCBs typically go up to 63A or 125A, so MCCBs are used for higher currents (roughly 16A to 1600A), as main incomers of buildings, panels and sub-panels, or where higher breaking capacity and adjustable settings are needed. MCCBs are covered by IS/IEC 60947-2.
Icu is the ultimate breaking capacity the MCCB can interrupt once, while Ics is the service breaking capacity it can interrupt and still remain usable. Choose an MCCB whose Icu exceeds the prospective fault current at the installation point; for critical feeders, a higher Ics (ideally 100% of Icu) is preferred.
Use 3 pole where only the phases need switching, and 4 pole where the neutral must also be isolated, such as generator changeover systems, incomers with unbalanced single-phase loads or where local rules require neutral isolation. Your panel designer or electrician should decide based on the earthing system.
Many MCCBs have an adjustable overload setting (for example 0.8 to 1 times the frame rating, or wider on electronic releases), and some allow short-circuit adjustment too. Fixed-release MCCBs cannot be adjusted, so check the release type before buying.
Common add-ons include auxiliary and trip alarm contacts, shunt trip and undervoltage releases, rotary handles for door mounting, motor operators for remote switching, and terminal spreaders or extended terminals for larger cables. Accessories are usually specific to the brand and frame size.