Legrand DPX³ 160 MCCB · 4P (FP) · 160 A · 50 kA · thermal magnetic · 420137: Elume price today ₹26,721 per pc incl. GST, 26% below the ₹36,110 MRP. The price has held steady for the last 30 days.
MCCB thermal magnetic - DPX³ 160 - Icu 50 kA - 400 V~ - 4P - 160 A. Breaking capacity of 50kA, according to EN/IEC standard 60947-2, suitable for protection of commercial and middle power installations - Compliant with NEMA AB‐1.
MCBs typically go up to 63A or 125A, so MCCBs are used for higher currents (roughly 16A to 1600A), as main incomers of buildings, panels and sub-panels, or where higher breaking capacity and adjustable settings are needed. MCCBs are covered by IS/IEC 60947-2.
Icu is the ultimate breaking capacity the MCCB can interrupt once, while Ics is the service breaking capacity it can interrupt and still remain usable. Choose an MCCB whose Icu exceeds the prospective fault current at the installation point; for critical feeders, a higher Ics (ideally 100% of Icu) is preferred.
Use 3 pole where only the phases need switching, and 4 pole where the neutral must also be isolated, such as generator changeover systems, incomers with unbalanced single-phase loads or where local rules require neutral isolation. Your panel designer or electrician should decide based on the earthing system.
Many MCCBs have an adjustable overload setting (for example 0.8 to 1 times the frame rating, or wider on electronic releases), and some allow short-circuit adjustment too. Fixed-release MCCBs cannot be adjusted, so check the release type before buying.
Common add-ons include auxiliary and trip alarm contacts, shunt trip and undervoltage releases, rotary handles for door mounting, motor operators for remote switching, and terminal spreaders or extended terminals for larger cables. Accessories are usually specific to the brand and frame size.