Schneider Schneider EasyLogic EM6400NG+ POP Energy Meter · 1P/3P · 1 A · METSEEM6400NGPOCL5 · METSEEM6400NGPOCL5
Rated current1 A
Ingress protectionIP51 front:· IP30 body:
Reference standardIEC 61010-1:ed. 3
Net weight0.6 kg
BrandSchneider
Brand SKUMETSEEM6400NGPOCL5
ELINEM34F6R49F
Sold asPer pc
RangeEasyLogic
SignalCurrent 0...12 A (impedance 0.3 MOhm)6 x · Voltage (impedance 5 MOhm)4 x
MaterialPolycarbonate
Display type7 segments LED
Product nameEM6400NG+ POP
Metering typeAverage current Iavg · Calculated neutral current · Reactive power Q, Q1, Q2, Q3 · Peak demand currents · Unbalance current · Demand current I1, I2, I3 · Peak demand power PM, QM, SM · Apparent power S, S1, S2, S3 · Phase currents · Average voltage Vavg · Voltage U21, U32, U13, V1, V2, V3 · Power factor and displacement PF (signed, four quadrant) · Demand power P, Q, S · Active power P, P1, P2, P3
Mounting modeFlush-mounted
Sampling rate64 samples/cycle
Accuracy classClass 5P total current harmonic distortion THD (I) conforming to IEC 61557-12 · Class 5P total voltage harmonic distortion THD (U) conforming to IEC 61557-12 · Class 0.5S active energy conforming to IEC 62053-22 · Class 1 reactive energy conforming to IEC 62053-24
Data recordingEnergy consumption logs
Display colourRed
Display digits12 digit(s) - 14.2 mm in height
Output voltage5...40 V DC@20 mA
type of network3P · 1P + N · 2P + N · 2P · 3P + N
Demand intervalsConfigurable from 1 to 60 min
Flame retardanceV-0 conforming to UL 94
Impulse duration20 ms
Local signallingGreen LED: activity · Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Mounting supportFramework
Network frequency50 Hz · 60 Hz
Number of outputs1 pulse
Tightening torqueCurrent circuit: 0.9…1 N.m Philips No 2 screwdriver · Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver · Control circuit: 0.9…1 N.m Philips No 2 screwdriver · Communication: 0.9…1 N.m Philips No 2 screwdriver
Device applicationPower monitoring
[In] rated current1 A · 5 A
Measurement current5…6000 mA
Measurement voltage35…480 V AC 45...65 Hz between phases · 35…277 V AC 45...65 Hz between phase and neutral · 35…600 V AC 45...65 Hz between phases · 35…347 V AC 45...65 Hz between phase and neutral · 600…999000 V AC 45...65 Hz with external VT
Type of measurementCurrent · Voltage · Frequency · Apparent energy · Apparent power · Active and reactive energy · Active and reactive power
Measurement accuracyCurrent +/- 0.5 % · Voltage +/- 0.5 % · Power +/- 0.5 % · Frequency +/- 0.05 % · Power factor +/- 0.01
Measurement categoryCategory III 480 V · Category II 480…600 V
Type of installationIndoor installation
Communication of dataReading of time-stamped measurements and events · Total energy · Energy metering · Net energy
Installation categoryIII
Wire stripping lengthCurrent circuit: 3.68 mm · Voltage circuit: 7 mm · Control circuit: 7 mm · Communication: 7 mm
Power quality analysistotal harmonic distortion
Connections - terminalsCurrent circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s) · Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Communication: screw clamp terminals 0.33…3.31 mm² cable(s)
Tamperproof of settingsProtected by access code
Messages display capacity3 fields of 4 characters
Product or component typeEnergy meter
[Us] rated supply voltage40...300 V AC 45...65 Hz · 40...300 V DC
Communication port support-
Communication port protocol-
Electrical insulation classClass II
Frequency measurement range45…65 Hz
Maximum power consumption in W2 W at 277 V
Maximum power consumption in VA6 VA at 277 V between phase and neutral
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.