Schneider Schneider Zelio Logic Analogue I/O Extension Module · 4 I O · 24 V DC · for Zelio Logic · SR3XT43BD · SR3XT43BD
Ingress protectionIP20 (terminal block)· IP40 (front panel)
Reference standardIEC 61000-4-12
Net weight0.11 kg
BrandSchneider
Brand SKUSR3XT43BD
ELINEFKK7M66JP
Sold asPer pc
LSB value0.15 °C, - 25...125 °C for analogue input circuit · 20 µA, 0...20 mA for analogue input circuit · 9.8 mV, 0...10 V for analogue input circuit · 9.8 mV, 0...10 V for analogue output
Load typeResistive load for analogue output
StandardsIEC 61000-4-12 · IEC 61000-4-5 · IEC 61000-4-3 · IEC 61000-4-4 level 3 · IEC 61000-4-6 level 3 · IEC 61000-4-2 level 3 · IEC 60068-2-6 Fc · IEC 61000-4-11 · IEC 60068-2-27 Ea
Conversion timeSmart relay cycle time for analogue input circuit · Smart relay cycle time for analogue output
Input impedance18 kOhm, input range: 0...10 V for analogue input circuit · 247 Ohm, input range: 0...20 mA for analogue input circuit
Repeat accuracy< +/- 0.3 °C, input range: - 25...125 °C at 25 °C for analogue input circuit · <= +/- 1 %, input range: 0...10 V at 25 °C for analogue input circuit · <= +/- 1 %, input range: 0...10 V at 55 °C for analogue output · <= +/- 1 %, input range: 0...20 mA at 25 °C for analogue input circuit
Conversion error+/- 1 % of the full scale value, input range: 0...10 V (25 °C) for analogue output · +/- 1 % of the full scale value, input range: 0...10 V (55 °C) for analogue output · +/- 1 %, input range: 0...10 V (25 °C) for analogue input circuit · +/- 1 %, input range: 0...10 V (55 °C) for analogue input circuit · +/- 1 %, input range: 0...20 mA (25 °C) for analogue input circuit · +/- 1 %, input range: 0..
Pollution degree2 conforming to IEC 61131-2
Range of productZelio Logic
Relative humidity95 % without condensation or dripping water
tightening torque0.5 N.m
Operating altitude2000 m
Operating distance10 m with screened cable for analogue input circuit · 10 m with screened cable for analogue output
Analogue input typeCommon mode
Analogue input range0...10 V · 0...20 mA · -25...125 °C
Maximum load current10 mA for analogue output
Analogue input number2
Analogue output range0...10 V
Analogue output number2
Product certificationsGOST · UL · C-Tick · CSA
Temperature probe typePt 100, 3-wire conforming to IEC 751
Connections - terminalsScrew terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) semi-solid · Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) solid · Screw terminals, 2 x 0.25...2 x 1.5 mm² (23 AWG...16 AWG) solid · Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end · Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end
IP degree of protectionIP20 (terminal block) conforming to IEC 60529 · IP40 (front panel) conforming to IEC 60529
Short-circuit protectionWith analogue output
Analogue input resolution10 bits on the input range
Product or component typeAnalogue I/O extension module
Analogue output resolution10 bits on the output range
Maximum altitude transport3048 m
Maximum permissible voltage30 V for analogue input circuit
Reverse polarity protectionAnalogue input circuit: with
Environmental characteristicEMC directive conforming to IEC 61000-6-2 · EMC directive conforming to IEC 61000-6-3 · EMC directive conforming to IEC 61000-6-4 · EMC directive conforming to IEC 61131-2 zone B · Low voltage directive conforming to IEC 61131-2
Disturbance radiated/conductedClass B conforming to IEC 55022-11 Group 1
[Imp] maximum permanent current30 mA for analogue input circuit
Ambient air temperature for storage-40…70 °C
Ambient air temperature for operation-20…40 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 · -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.