EasyLogic PFC Plus range of capacitors is dedicated to applications where a few non-linear loads are present. These capacitors are designed for use with detuned reactors to deliver a perfect balance between performance and cost. This capacitor provides a rated output power of 30,6kVar at 525V AC, 50Hz. Fastening assured by a Stud terminal.
It depends on your load and the existing power factor; the required kVAR equals kW times (tan of the present PF angle minus tan of the target PF angle). For example, raising 100 kW from 0.8 to 0.98 PF needs about 55 kVAR; an electrical consultant can size it from your bills or a load survey.
Higher voltage ratings give a safety margin against supply overvoltage and harmonics, which increases capacitor life. With detuned reactors, the capacitor voltage rises further, so 480V or higher is commonly used.
Standard MPP (metallised polypropylene) capacitors suit clean loads, heavy-duty types handle higher inrush and temperatures, and gas-filled or oil-filled types offer better heat dissipation and longer life. Choose based on harmonic level, switching frequency and panel temperature (self-healing LT power capacitors are covered by IS 13340, aligned with IEC 60831).
If your site has many non-linear loads such as VFDs, UPS, LED lighting or rectifiers, harmonics can damage capacitors and cause resonance, so detuned reactors (typically 7% or 14%) are recommended. A harmonic measurement helps decide.
Capacitor duty contactors with pre-charge resistors are recommended because they limit the high inrush current when a capacitor is switched in. Normal contactors can weld or wear out quickly in APFC panels.