This time delay unit is an auxiliary that can be combined with an undervoltage release (MN). It must be associated with a 380-480 VAC MN undervoltage release. It eliminates the risk of nuisance tripping due to transient voltage dips lasting from 200ms to 3s. Its power supply is 380-480VDC or 380-480VAC 50/60Hz. This time delay unit has 4 adjustable steps (0.5s - 1s - 1.5s - 3s). It is an external accessory and can be mounted in the switchboard.
An on-delay timer switches its output after the set time once it receives power or a start signal, while an off-delay timer holds its output on for the set time after the signal is removed. Multifunction timers offer both and other modes such as cyclic and interval.
A dedicated star-delta timer has a built-in short dead time between star and delta changeover to prevent a short circuit across contactors. The star time is set to suit how fast the motor reaches near full speed, often a few seconds to around 15 seconds.
A phase monitoring relay detects phase loss, phase reversal (wrong sequence) and often phase unbalance or under/over voltage, and trips the contactor coil to protect three-phase motors. It is especially useful for pumps, compressors and lifts where wrong rotation or single phasing can cause damage.
A cyclic or programmable timer can switch a pump contactor on and off at set intervals, but for tank level control a level controller relay with probes or a float switch is more reliable. The pump also needs proper motor protection like an MPCB or overload relay.
Most modern timers and monitoring relays are DIN rail mounted (35mm), while some older or plug-in types use an 8-pin or 11-pin socket base. Check the mounting type and whether the base is included.