Schneider Schneider EasyLogic PM1130H Energy Meter · 1P/3P · 5 A · Class 2 reactive energy · Class 0.5 · METSEPM1130HCL05RD · METSEPM1130HCL05RD
Rated current5 A
Ingress protectionIP51 front:· IP30 body:
Reference standardIEC 61010-1:ed. 3
Net weight0.3 kg
BrandSchneider
Brand SKUMETSEPM1130HCL05RD
ELINE6H9RFCMP2
Sold asPer pc
RangeEasyLogic
SignalVoltage (impedance 5 MOhm)4 x · Current 0.005...10 A (impedance 0.3 MOhm)6 x
MaterialPolycarbonate
Display type7 segments LED
Product nameEasyLogic PM11XXH RS
Metering typeCalculated neutral current · Rotation speed · Phase currents · Active power P, P1, P2, P3 · Unbalance current · Power factor and displacement PF (signed, four quadrant) · Active, reactive, apparent energy (signed, two quadrant) · Reactive power Q, Q1, Q2, Q3 · Apparent power S, S1, S2, S3 · Demand power P, Q, S · Frequency · Voltage U21, U32, U13, V1, V2, V3 · Unbalance voltage · Phase current I1,
Mounting modeFlush-mounted
Sampling rate32 samples/cycle
Accuracy classClass 2 reactive energy conforming to IEC 62053-23 · Class 0.5 active energy conforming to IEC 62053-22
Data recordingEnergy consumption logs
Display colourRed
Display digits12 digit(s) - 14.2 mm in height
Output voltage300 V AC@2 A
type of network3P + N · 3P · 2P · 1P + N · 2P + N
Demand intervals1 s
Flame retardanceV-0 conforming to UL 94
Local signallingGreen LED: activity · Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) · Red LED: alternate source
Mounting supportFramework
Counter functionsPower interruption · ON-load source 1 hour counting · ON-load source 2 hour counting · ON hour counting
Device short namePM1130H
Network frequency60 Hz · 50 Hz
Number of outputs1 relay
Device applicationMain or redundant power monitoring · Energy monitoring
Provided equipmentInstallation guide
[In] rated current5 A · 1 A
Measurement current5…6000 mA
Measurement voltage35…480 V AC 50...60 Hz between phases · 35…277 V AC 50...60 Hz between phase and neutral · 277…999000 V AC 50...60 Hz with external VT
Type of measurementCurrent · Voltage · Frequency · Power factor · Phase angle · RPM · Peak demand power · Harmonic distortion (I THD & U THD) · Active power · Active energy
Measurement accuracyCurrent +/- 0.5 % · Voltage +/- 0.5 % · Frequency +/- 0.05 % · Power factor +/- 0.01 · Reactive power +/- 2 % · Reactive energy +/- 2 % · Active power +/- 0.5 % · Apparent power +/- 0.5 % · Active energy +/- 0.5 % · Apparent energy +/- 0.5 % · Harmonic distortion (I THD & U THD) +/- 5 %
Measurement categoryCategory III 480 V
Type of installationIndoor installation
Communication of dataReading of measurements · All counters · Instantaneous and demand values · Last cleared log · Revolution speed
Installation categoryIII
Power quality analysistotal harmonic distortion
Connections - terminalsCurrent circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s) · Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Communication: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s) · Secondary circuit: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s) · Relay output: screw clamp terminals (rear
Tamperproof of settingsProtected by access code
Messages display capacity3 fields of 4 characters
Product or component typeDual source energy meter
[Us] rated supply voltage60...277 V AC 45...65 Hz · 60...277 V DC
Communication port supportRS485
Communication port protocolModbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
Electrical insulation classClass II
Frequency measurement range45…65 Hz
Maximum power consumption in W3 W at 240 V
Maximum power consumption in VA6 VA at 240 V between phase and neutral
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.