This is an accessory for Micrologic trip unit for Compact NSX and PowerPact multistandard devices. It is an external battery used for the local inspection and testing of Micrologic trip units. It enables to use Micrologic display screen and keypad even if the power supply to the Micrologic trip unit is interrupted. The pocket battery is connected to Micrologic test port with the trip unit connector (supplied with the pocket battery). Additionally, the pocket battery embeds a plastic screw-driver for the rotary switches settings and a flash light.
MCBs typically go up to 63A or 125A, so MCCBs are used for higher currents (roughly 16A to 1600A), as main incomers of buildings, panels and sub-panels, or where higher breaking capacity and adjustable settings are needed. MCCBs are covered by IS/IEC 60947-2.
Icu is the ultimate breaking capacity the MCCB can interrupt once, while Ics is the service breaking capacity it can interrupt and still remain usable. Choose an MCCB whose Icu exceeds the prospective fault current at the installation point; for critical feeders, a higher Ics (ideally 100% of Icu) is preferred.
Use 3 pole where only the phases need switching, and 4 pole where the neutral must also be isolated, such as generator changeover systems, incomers with unbalanced single-phase loads or where local rules require neutral isolation. Your panel designer or electrician should decide based on the earthing system.
Many MCCBs have an adjustable overload setting (for example 0.8 to 1 times the frame rating, or wider on electronic releases), and some allow short-circuit adjustment too. Fixed-release MCCBs cannot be adjusted, so check the release type before buying.
Common add-ons include auxiliary and trip alarm contacts, shunt trip and undervoltage releases, rotary handles for door mounting, motor operators for remote switching, and terminal spreaders or extended terminals for larger cables. Accessories are usually specific to the brand and frame size.