Siemens Betagard 5SV4 RCCB 40 A (article 5SV46140RC) is a rccb from Siemens, 5SV4 series, sold by Elume with a GST invoice and pan-India delivery. Key data: manufacturer product name RES.CUR.OP.CIRCUIT BREAKER TYPE AC 40A 1+N-POLE 300MA 240V 2MW INDIA, ampere/current rating 40 A, no. of poles 2 Pole, rated voltage (v) 240V AC, tripping characteristic Type AC, tripping sensitivity 300 mA. Priced at the Siemens India list price of 2026 (MRP before GST Rs 7,310), GST included in the price shown.
For protecting people from shock, use 30mA on circuits feeding sockets, bathrooms, kitchens and outdoor points. 100mA or 300mA RCCBs are mainly for fire protection and are often used upstream as a main device, with 30mA protection on the final circuits.
Yes. An RCCB only detects earth leakage and does not protect against overload or short circuit, so it must be backed up by an MCB or fuse of a rating given in the manufacturer's data (RCCBs are covered by IS 12640 (Part 1)).
Common causes are genuine leakage from a faulty appliance (often a geyser element, pump or washing machine), moisture in wiring, neutral of one circuit being shared with another, or many electronic loads adding up their small leakages. Switch off all MCBs and turn them on one by one to find the culprit circuit, and have an electrician test insulation; never bypass the RCCB.
Type AC detects only sinusoidal AC leakage, while Type A also detects pulsating DC leakage produced by electronic loads like inverter ACs, washing machines, induction cooktops and LED drivers. Type A is the safer choice for modern homes with many electronic appliances; EV chargers and VFDs may need Type B or a charger with built-in DC detection.
Manufacturers commonly recommend pressing the test button regularly, often once a month; check the interval in the product's instructions. The RCCB should trip immediately, and if it does not, have an electrician check and replace it.
The RCCB's rated current should be equal to or higher than the MCB or main switch feeding it, because it must carry the full load current. Many Indian homes use 40A or 63A RCCBs at the incomer; for a single circuit, 25A is common.