🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
ABB XT5N 400 TMA 320-3200 3p F F · 1SDA100344R11SDA100344R1↓ 53% off MRP
BrandABB
CategorySwitchgear
SpecificationC.BREAKER TMAX XT5N 400 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 320 I3=1600...3200
Brand SKU1SDA100344R1
AvailabilityOut of stock
DeliveryPan-India · 7 working days
ABB· Out of stock
Visit the ABB store

ABB XT5N 400 TMA 320-3200 3p F F · 1SDA100344R1

₹31,232/pcincl. GST-53%
₹26,468 + 18% GST · MRP ₹66,171
Out of stock

We list this so you can see the spec and our price, but it cannot be ordered right now. Email info@elumenuvo.com and we will source it for you.

💳 30 Day credit facility available launching soon - join waitlist.

ABB XT5N 400 TMA 320-3200 3p F F · 1SDA100344R1: Elume price today ₹31,232 per pc incl. GST, 53% below the ₹66,171 MRP. The price has held steady for the last 30 days. The average price across the sellers we track is ₹23,796, ₹7,436 less than here.

Price history
Elume price vs the average market price across the sellers we track, day by day. Tap a legend entry to show or hide a line.
25 May to 22 Nov
₹70,803₹57,752₹44,702₹31,651₹18,601₹66,171₹31,232₹23,796
May 26Jun 26Aug 26Sep 26Oct 26Nov 26Nov 26
Elume today
₹31,232
Avg market price
₹23,796
MRP
₹66,171
Lowest in view · 10 Aug
₹20,001
Highest in view · 3 Oct
₹31,232
🏷️
100% genuine
Brand-authorised stock with full manufacturer warranty
🧾
GST invoice
Tax invoice on every order · GST billing with tax split
🚚
Pan-India delivery
7 working days to your location
📦
Wholesale built in
Wholesale price at 15+ units: ₹29,670/pc on this product, applied automatically

ABB XT5N 400 TMA 320-3200 3p F F is an MCCB from ABB. It protects feeders and sub-mains against overload and short circuit and is the incomer or outgoing breaker of a panel. Key ratings: Poles 3P (TP), Rated current 320 A, Icu 36 kA, Release TMA, Setting range 224…320 A, Rated voltage 690 V AC. It is built to IEC60947-2.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB XT5N 400 TMA 320-3200 3p F F · 1SDA100344R1 · 1SDA100344R1
Device typeMoulded case circuit breaker (MCCB)
SeriesSACE Tmax XT
Frame size400 A
Poles3P (TP)
Rated current320 A
Rated voltage690 V AC
Ultimate breaking capacity (Icu)36 kA
Service breaking capacity (Ics)36 kA
Setting range224…320 A
ReleaseTMA
Insulation voltage (Ui)1000 V
Impulse withstand (Uimp)8 kV
Reference standardIEC60947-2
Net weight4.775 kg
Country of originItaly
BrandABB
Brand SKU1SDA100344R1
ELINEM2H24JKCC
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet 1SDC210100D0206; Product name; shop.in.abb.com listing for 1SDA100344R1, 23 Sep 2026). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.
No reviews yet