🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
ABB OT315E02P SWITCH-DISCONNECTOR · 1SCA022866R55901SCA022866R5590↓ 53% off MRP
BrandABB
CategorySwitchgear
SpecificationOT315E02P · OT
Brand SKU1SCA022866R5590
AvailabilityIn stock · ships in 24h
DeliveryPan-India · 7 working days
ABB· In stock
Visit the ABB store

ABB OT315E02P SWITCH-DISCONNECTOR · 1SCA022866R5590

NEW added this week
₹9,322/pcincl. GST-53%
₹7,900 + 18% GST · MRP ₹19,751
Add to cart
Buy now
  • Secured by Razorpay · UPI, cards, net banking, wallets
  • GST invoice, claim input tax credit
  • Tracked delivery, 5 to 7 working days
✓ Full brand warranty on every order
✓Lowest price guarantee · found it cheaper? We match it.
💳 30 Day credit facility available launching soon - join waitlist.
₹9,322 /pc incl. GST
Free pan-India delivery

ABB OT315E02P SWITCH-DISCONNECTOR · 1SCA022866R5590: Elume price today ₹9,322 per pc incl. GST, 53% below the ₹19,751 MRP. The price has held steady for the last 30 days.

Price history
Elume price over time, day by day. Market comparison appears once we track this item.
16 Nov to 22 Nov
₹21,134₹18,018₹14,902₹11,785₹8,669₹19,751₹9,322
16 Nov17 Nov18 Nov19 Nov20 Nov21 Nov22 Nov
Elume today
₹9,322
MRP
₹19,751
Lowest in view · 17 Nov
₹9,322
🏷️
100% genuine
Brand-authorised stock with full manufacturer warranty
🧾
GST invoice
Tax invoice on every order · GST billing with tax split
🚚
Pan-India delivery
7 working days to your location
📦
Wholesale built in
Wholesale price at 15+ units: ₹8,856/pc on this product, applied automatically

2-pole, front operated, base mounted switch-diconnector with black IP65 handle and shaft, terminal bolt kit included

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB OT315E02P SWITCH-DISCONNECTOR · 1SCA022866R5590 · 1SCA022866R5590
Device typeIsolator (switch disconnector)
SeriesOT
Poles2P (DP)
Rated voltage1000 V
Impulse withstand (Uimp)12 kV
Reference standardIEC 60947-3
Country of originFinland
BrandABB
Brand SKU1SCA022866R5590
ELINEGDRP4K2HJ
Sold asPer pc
StandardsIEC 60947-3
Mounting TypeBase mounting
Package Width210 mm, 8.3 inch
Product ClassSwitch-disconnectors
Package Height150 mm, 5.9 inch
Package Length210 mm, 8.3 inch
Number of Poles2
Package Gross Weight2.5 kg, 5.5 pound
Extended Product TypeOT315E02P
Rated Operational VoltageMain Circuit 1000 V
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Short-time Withstand Current (Icw)for 1 s 15 kA
Product RangeOT
Ratings as published by ABB (shop.in.abb.com listing for 1SCA022866R5590, 15 Nov 2026). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.
What is the difference between an isolator and an MCB?

An isolator (switch-disconnector) only switches the circuit on and off and does not trip on overload or short circuit, while an MCB provides protection. Isolators are used as main switches in DBs or near equipment for safe maintenance, and must be backed by a suitable MCB, MCCB or fuse.

Can I use an isolator as the main switch in my DB?

Yes, a DP isolator for single-phase or 4P isolator for three-phase is commonly used as the DB incomer, provided protection is given upstream (by the meter-side fuse or MCB) and on each outgoing circuit. Its current rating should be equal to or higher than the upstream protection rating.

Is this isolator safe to switch on load?

Switch-disconnectors to IS/IEC 60947-3 are rated for switching under load according to their utilisation category, such as AC-22 for mixed resistive and inductive loads or AC-23 for motor loads. Check the category on the product before using it to switch motors directly.

2 pole or 4 pole isolator - which one do I need?

Use 2 pole for single-phase supply (phase and neutral) and 4 pole for three-phase supply with neutral, so all live conductors are disconnected during maintenance. A 3 pole isolator is used where no neutral is switched, such as some motor feeders.

Can an isolator be locked off for maintenance?

Many isolators and rotary switch-disconnectors have a padlocking provision in the OFF position so no one can switch them on while work is in progress. Check for the lock-off feature if it is needed for your site's safety procedures.

No reviews yet