ABB XT5N 630 Ekip Dip LSIG In=630 4p F F · 1SDA100405R11SDA100405R1↓ 53% off
BrandABB
CategorySwitchgear
SpecificationXT5N 630 Ekip Dip LSIG In=630 4p F F · TMax XT
Brand SKU1SDA100405R1
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB XT5N 630 Ekip Dip LSIG In=630 4p F F · 1SDA100405R1

$1,222.57/pc-53%
$2,590.20
Wholesale · 15+ units
$1,161.44 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$1,222.57 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $1,161.44/pc on this product, applied automatically

C.BREAKER TMAX XT5N 630 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP DIP LSIG R 630

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB XT5N 630 Ekip Dip LSIG In=630 4p F F · 1SDA100405R1 · 1SDA100405R1
Device typeMoulded case circuit breaker (MCCB)
SeriesTMax XT
Rated current630 A
Rated voltage690 V AC
Service breaking capacity (Ics)70 kA
ReleaseEL
Insulation voltage (Ui)1000 V
Impulse withstand (Uimp)8 kV
Country of originItaly
Poles4-pole
Reference standardIS/IEC 60898-1
BrandABB
Brand SKU1SDA100405R1
ELINE6G3M9JJ6K
Sold asPer pc
Sub-typeXT5
Release TypeEL
Package Width250 mm
Product ClassMoulded Case Circuit Breakers
Package Height245 mm
Package Length285 mm
Package Gross Weight6.888 kg
Electrical Durability5000 cycle
Extended Product TypeXT5N 630 Ekip Dip LSIG In=630 4p F F
Rated Operational Voltage690 V AC
Rated Insulation Voltage (Ui)1000 V
Rated Uninterrupted Current (Iu)630 A
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Short-time Withstand Current (Icw)6 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 70 kA
Product RangeTMax XT
Ratings as published by ABB (shop.in.abb.com listing for 1SDA100405R1, 15 Nov 2026). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.