🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
ABB CT-TGC.22 Time relay, Pulse generator 2c/o, 24-48VDC/24-240VAC · 1SVR508160R01001SVR508160R0100↓ 53% off
BrandABB
CategorySwitchgear
SpecificationCT-TGC.22 · Time Relays
Brand SKU1SVR508160R0100
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB CT-TGC.22 Time relay, Pulse generator 2c/o, 24-48VDC/24-240VAC · 1SVR508160R0100

$82.32/pc-53%
$174.37
Wholesale · 15+ units
$78.20 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$82.32 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $78.20/pc on this product, applied automatically

The CT-TGC.22 is a single-function electronic time relay from the CT-C timer range. It provides a pulse generator (recycling unequal times) function with 2x7 time ranges from 0.05 s to 100 h. This time relay operates with a rated control supply voltage of 24 - 48 V DC / 24 - 240 V AC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. A control input works with voltage-related (non-floating) triggering.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB CT-TGC.22 Time relay, Pulse generator 2c/o, 24-48VDC/24-240VAC · 1SVR508160R0100 · 1SVR508160R0100
Device typeRelay
SeriesTime Relays
Frequency50 / 60 Hz
Insulation voltage (Ui)Input Circuit / Output Circuit 300 V
Country of originBulgaria
Reference standardIS/IEC 60898-1
BrandABB
Brand SKU1SVR508160R0100
ELINEJF73D3D26
Sold asPer pc
Package Width89 mm
Terminal TypeScrew Terminals
Package Height65 mm
Package Length20 mm
Rated Frequency (f)50 / 60 Hz
Package Gross Weight0.079 kg
Extended Product TypeCT-TGC.22
Ambient Air TemperatureOperation -20 ... +60 °C
Max Operating Voltage UL/CSAOutput Circuit 300 V AC
Rated Insulation Voltage (Ui)Input Circuit / Output Circuit 300 V
Product RangeTime Relays
Ratings as published by ABB (shop.in.abb.com listing for 1SVR508160R0100, 15 Nov 2026). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.