ABB 24 V AC/DC Relay · CT-ARE Time relay · true OFF-delay 1c/o · 0.1-10s · 220-240 V AC · 1SVR550127R11001SVR550127R1100↓ 5% off
BrandABB
CategorySwitchgear
SpecificationRelay · 4 A · 240 V AC
Brand SKU1SVR550127R1100
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB 24 V AC/DC Relay · CT-ARE Time relay · true OFF-delay 1c/o · 0.1-10s · 220-240 V AC · 1SVR550127R1100

$24.72/pc-5%
$25.96
Wholesale · 15+ units
$23.49 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$24.72 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $23.49/pc on this product, applied automatically

The CT-ARE is a single-function electronic time relay from the CT-E timer range. It provides an OFF-delay (true delay on break) function without auxiliary voltage and with a time range from 0.1 s to 10 s. This time relay operates with a rated control supply voltage of 24 V AC / DC / 220 - 240 V AC and has a 1 c/o (SPDT) output rated at 250 V / 4 A.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB 24 V AC/DC Relay · CT-ARE Time relay · true OFF-delay 1c/o · 0.1-10s · 220-240 V AC · 1SVR550127R1100 · 1SVR550127R1100
Device typeRelay
Rated current4 A
Rated voltage240 V AC
Width1.5 modules (22.5 mm)
Reference standardCAN/CSA C22.2 No.14, IEC/EN 63000, IEC/EN 61812-1, UL 508
Net weight0.07 kg
Current rating4 A
BrandABB
Brand SKU1SVR550127R1100
ELINEK9DDKG4PF
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet 2CDC111138D0201; Product name). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.