ABB ABB AF2050-30-11 100-250V 50/60Hz / 100-250 DC Contactor · 1SFL707001R7011 · 1SFL707001R7011
Device typeContactor
SeriesAF Contactors
Poles3P (TP)
Frequency50/60 Hz
Insulation voltage (Ui)acc. to UL/CSA 600 V, acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Country of originSweden
Reference standardIS/IEC 60898-1
BrandABB
Brand SKU1SFL707001R7011
ELINEH7F9GR2CF
Sold asPer pc
Operate TimeBetween Coil De-energization and NC Contact Closing 35 ... 55 millisecond, Between Coil De-energization and NO Contact Opening 35 ... 55 millisecond, Between Coil Energization and NC Contact Opening 50 ... 80 millisecond, Between Coil Energization and NO
Package Width555 mm
Product ClassBlock Contactors
Terminal TypeMain Circuit: Bars
Package Height500 mm
Package Length365 mm
Number of Poles3
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 48 V - A, Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V - A, Holding at Max. Rated Control Circuit Voltage DC 20.5 V - A, Pull-in at Max. Rated Control Circuit Voltage
Rated Frequency (f)Main Circuit 50/60 Hz
Mounted Aux Contacts1 NO, 1 NC
Package Gross Weight35 kg
Extended Product TypeAF2050-30-11-70
Rated Frequency Limits25 ... 400 Hz
Ambient Air TemperatureClose to Contactor for Storage -40 ... +70 °C, Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C, Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C
General Use Rating UL/CSA(600 V AC) 2100 A
Number of Aux Contacts NC1
Number of Aux Contacts NO1
Number of Main Contacts NC0
Number of Main Contacts NO3
Max Operating Voltage UL/CSAMain Circuit 600 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V, acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Operational Power AC-3 (Pe)(1000 V) 630 KWT, (415 V) 630 KWT, (440 V) 710 KWT, (690 V) 1000 KWT
Max Electrical Switching FrequencyAC-1 60 cycles per hour
Max Mechanical Switching Frequency300 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 100-250V; 60 Hz 100-250V; DC Operation 100-250V
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 2050 A, (1000 V) 55 °C 1750 A, (1000 V) 70 °C 1500 A, (690 V) 40 °C 2050 A, (690 V) 55 °C 1750 A, (690 V) 70 °C 1500 A
Rated Operational Current AC-3 (Ie)(220 / 230 / 240 V) 55 °C 1060 A, (380 / 400 V) 55 °C 1060 A, (415 V) 55 °C 1060 A, (440 V) 55 °C 1060 A, (500 V) 55 °C 970 A, (690 V) 55 °C 970 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 40 °C 2050 A, (600 V) 3 Poles in Series, 40 °C 2050 A, (850 V) 3 Poles in Series, 40 °C 2050 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 40 °C 2050 A, (600 V) 3 Poles in Series, 40 °C 2050 A, (850 V) 3 Poles in Series, 40 °C 2050 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 40 °C 2050 A, (600 V) 3 Poles in Series, 40 °C 2050 A, (850 V) 3 Poles in Series, 40 °C 2050 A
Rated Short-time Withstand Current (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 10000 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 2200 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 5500 A, at 40 °C Ambient Temp, in Free Air,
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 2050 A
Automation & Control Rated Operational VoltageMain Circuit 1000 V
Rated Making Capacity AC-3 acc. to IEC 60947-4-110 x Ie AC-3
Product RangeAF Contactors
Ratings as published by ABB (shop.in.abb.com listing for 1SFL707001R7011, 15 Nov 2026). Verify critical parameters against the datasheet before specifying.