🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
ABB XT2N 160 Ekip LS/I In=160 A 4pFF InN=100% · 1SDA067095R11SDA067095R1↓ 53% off
BrandABB
CategorySwitchgear
SpecificationC.BREAKER TMAX XT2N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LS/I R 160 A FULLY RATED NEUTRAL
Brand SKU1SDA067095R1
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB XT2N 160 Ekip LS/I In=160 A 4pFF InN=100% · 1SDA067095R1

$516.01/pc-53%
$1,093.21
Wholesale · 15+ units
$490.21 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$516.01 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $490.21/pc on this product, applied automatically

ABB XT2N 160 Ekip LS/I In=160 A 4pFF InN=100% is an MCCB from ABB. It protects feeders and sub-mains against overload and short circuit and is the incomer or outgoing breaker of a panel. Key ratings: Poles 4P (FP), Rated current 160 A, Icu 36 kA, Release Ekip Dip LS/I, Rated voltage 690 V AC. It is built to IEC60947-2.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB XT2N 160 Ekip LS/I In=160 A 4pFF InN=100% · 1SDA067095R1 · 1SDA067095R1
Device typeMoulded case circuit breaker (MCCB)
SeriesSACE Tmax XT
Poles4P (FP)
Rated current160 A
Rated voltage690 V AC
Frequency50 / 60 Hz
Ultimate breaking capacity (Icu)36 kA
Service breaking capacity (Ics)36 kA
ReleaseEkip Dip LS/I
Insulation voltage (Ui)1000 V
Impulse withstand (Uimp)8 kV
Terminal capacityBusbar 32.5..100 mm²
Reference standardIEC60947-2
Net weight1.6 kg
Country of originItaly
Current rating160 A
BrandABB
Brand SKU1SDA067095R1
ELINEHRH6CRC4M
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet SDC210100D0206; shop.in.abb.com listing for 1SDA067095R1, 23 Sep 2026; Product name). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.
No reviews yet