🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
ABB TEF4-ON Frontal Electronic Timer · 1SBN020112R10001SBN020112R1000↓ 53% off
BrandABB
CategorySwitchgear
SpecificationTEF4-ON · AF Contactors
Brand SKU1SBN020112R1000
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB TEF4-ON Frontal Electronic Timer · 1SBN020112R1000

$98.58/pc-53%
$208.83
Wholesale · 15+ units
$93.65 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$98.58 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $93.65/pc on this product, applied automatically

TEF4 frontal electronic timers are used for realizing timing function and are available in ON-delay and OFF-delay versions. Compact solution in cabinet compared to separate timers TEF4 electronic timers are front-mounted and locked on AF contactors or NF contactor relays. A mechanical indicator allows to show the state of the contactor. Safe and cost-reduced wiring. TEF4 electronic timers are supplied by a direct plug-in parallel connection to the coil terminals A1 - A2 of the contactor or contactor relay. A varistor is integrated on the timer to offer a built-in protection against surges in the contactor coil. Available for a wide control voltage range 24...240 V AC/DC TEF4-ON or TEF4-OFF allow time-delayed functions up to 100 s in 3 distinct time ranges, independently of the control system. The time delay ranges are selected by a switch and the time delay can be adjusted by means of a rotary switch. The timing function is activated by closing or opening the device on which the timer is mounted. The OFF-delay version operates without additional control supply.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB TEF4-ON Frontal Electronic Timer · 1SBN020112R1000 · 1SBN020112R1000
SeriesAF Contactors
FrequencyAuxiliary Circuit 50 / 60 Hz
Insulation voltage (Ui)acc. to UL/CSA 300 V, acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 400 V
Country of originChina
Device typeMiniature circuit breaker (MCB)
Reference standardIS/IEC 60898-1
BrandABB
Brand SKU1SBN020112R1000
ELINEM9H6RR7K4
Sold asPer pc
Package Width82 mm
Product ClassBlock Contactors Accessories
Terminal TypeScrew Terminals
Package Height51 mm
Package Length56 mm
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Package Gross Weight0.065 kg
Extended Product TypeTEF4-ON
Ambient Air TemperatureClose to Contactor for Storage -40 ... +80 °C, Near Contactor for Operation in Free Air -25 ... +70 °C
Contactors Setting Range0.1 ... 100 second [unit of time]
Number of Aux Contacts NC1
Number of Aux Contacts NO1
Rated Insulation Voltage (Ui)acc. to UL/CSA 300 V, acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 400 V
Max Electrical Switching FrequencyAC-15 1200 cycles per hour, DC-13 900 cycles per hour
Max Mechanical Switching Frequency3600 cycles per hour
Rated Operational Current AC-15 (Ie)(220 / 240 V) 1.5 A, (24 / 127 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 1 A / 24 W
Rated Short-time Withstand Current (Icw)for 0.1 s 8 A, for 1 s 8 A
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-5-1, q = 40 °C 5 A
Product RangeAF Contactors
Ratings as published by ABB (shop.in.abb.com listing for 1SBN020112R1000, 15 Nov 2026). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.