🚚 Free delivery over ₹4,000 pan-India · we also ship worldwide · Buying in bulk? Get a quote in 24 hours →
ABB MO132-20 Manual Motor Starter Magnetic Only · 1SAM360000R10131SAM360000R1013↓ 53% off
BrandABB
CategorySwitchgear
SpecificationManual motor starter (MPCB) · 3P (TP) · 20.0 A · 25 kA · 690 V AC · 100 kA
Brand SKU1SAM360000R1013
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB MO132-20 Manual Motor Starter Magnetic Only · 1SAM360000R1013

$120.59/pc-53%
$255.47
Wholesale · 15+ units
$114.57 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$120.59 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $114.57/pc on this product, applied automatically

The MO132-20 manual motor starter magnetic only is a compact 45 mm width device with a rated operational current of Ie = 20.0 A. This device is used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 25 kA at 400 V AC. A combination togethe

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB MO132-20 Manual Motor Starter Magnetic Only · 1SAM360000R1013 · 1SAM360000R1013
Device typeManual motor starter (MPCB)
Poles3P (TP)
Rated current20 A
Breaking capacity25 kA
Rated voltage690 V AC
Frequency50 Hz
Ultimate breaking capacity (Icu)100 kA
Service breaking capacity (Ics)100 kA
Operational current (Ie)20 A
Setting rangeNone
Insulation voltage (Ui)690 V
Impulse withstand (Uimp)6 kV
Width2.5 modules (45 mm)
Terminal capacityFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Ingress protectionIP20
Reference standardIEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L
Net weight0.31 kg
Country of originGermany
Current rating0 A
BrandABB
Brand SKU1SAM360000R1013
ELINE492RP4G2C
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet 2CDC131035D0202; shop.in.abb.com listing for 1SAM360000R1013, 23 Sep 2026; Product name). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.
No reviews yet