ABB MS132-1.0 Manual Motor Starter · 1SAM350000R10051SAM350000R1005↓ 53% off
BrandABB
CategorySwitchgear
SpecificationManual motor starter (MPCB) · 3P (TP) · 1.00 A · 690 V AC · 100 kA · 0.63 ... 1.0 A
Brand SKU1SAM350000R1005
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB MS132-1.0 Manual Motor Starter · 1SAM350000R1005

$88.77/pc-53%
$188.10
Wholesale · 15+ units
$84.33 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$88.77 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $84.33/pc on this product, applied automatically

The MS132-1.0 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 1.00 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated s

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB MS132-1.0 Manual Motor Starter · 1SAM350000R1005 · 1SAM350000R1005
Device typeManual motor starter (MPCB)
Poles3P (TP)
Rated current1 A
Rated voltage690 V AC
Frequency50 Hz
Ultimate breaking capacity (Icu)100 kA
Service breaking capacity (Ics)100 kA
Operational current (Ie)1 A
Setting range0.63 ... 1.0 A
Insulation voltage (Ui)690 V
Impulse withstand (Uimp)6 kV
Width2.5 modules (45 mm)
Terminal capacityFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Ingress protectionIP20
Reference standardIEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L
Net weight0.215 kg
Country of originGermany
Current rating00 A
Breaking capacity100 kA
BrandABB
Brand SKU1SAM350000R1005
ELINE9G46R6222
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet 2CDC131021D0202; shop.in.abb.com listing for 1SAM350000R1005, 23 Sep 2026; Product name). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.