ABB AA1-24 Shunt Trip · 1SAM201910R10011SAM201910R1001↓ 53% off
BrandABB
CategorySwitchgear
SpecificationAA1-24 Shunt Trip 20-24V
Brand SKU1SAM201910R1001
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
ABB· In stock
Visit the ABB store

ABB AA1-24 Shunt Trip · 1SAM201910R1001

$56.05/pc-53%
$118.75
Wholesale · 15+ units
$53.25 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$56.05 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $53.25/pc on this product, applied automatically

Shunt trips AA1 release manual motor starters used for remote tripping. They are attached laterally on the left side of MS116, MS132 or MS165. In accordance with IEC 60947-1, the manual motor starter is switched off by AA1 if the supply voltage of the shunt trip measured during the tripping operation remains between 70% and 110% of the rated control circuit supply voltage.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB AA1-24 Shunt Trip · 1SAM201910R1001 · 1SAM201910R1001
FrequencyAuxiliary Circuit 50 Hz
Insulation voltage (Ui)690 V
Impulse withstand (Uimp)Auxiliary Circuit 6 kV
Reference standardCSA 22.2 No. 14, IEC/EN 60947-1, IEC/EN 60947-4-1, UL 508, UL 60947-1, UL 60947-4-1
Net weight0.1 kg
Country of originGermany
Device typeMiniature circuit breaker (MCB)
BrandABB
Brand SKU1SAM201910R1001
ELINE3JR2DG9RG
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet 1SBC100214C0202; shop.in.abb.com listing for 1SAM201910R1001, 23 Sep 2026). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.