This Acti9 iPRC product is a surge arrester protecting against overvoltage related to lightning strikes. The DC power supply inputs up to 53V and AC power supply inputs up to 37V. The iPRI surge arrester protects the measuring instrument and PLC "sensor" inputs. It protects for 2 low-current lines without common potential or 4 lines with common reference potential. The input current must not exceed 300mA. The Uc maximum continuous operating voltage in common mode (between neutral and earth) is 130VAC or 185VDC. The Uc maximum continuous operating voltage in differential mode (between pgase and neutral) is 130VAC or 185VAC. The Up Voltage protection level in differential mode (between phase and neutral) is 160V. The Up Voltage protection level in common mode (between phase and earth) is 200V. The Ue rated operational voltage is 130VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 18mm x (H) 90mm x (D) 66mm. The weight is 25g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C.
For most homes and apartments, a Type 2 SPD in the main DB is the standard choice. Type 1 or combined Type 1+2 is used at the service entrance of independent houses in lightning-prone areas or buildings with external lightning protection (SPDs are covered by IS 16463 (Part 11), identical to IEC 61643-11).
Yes. An SPD diverts surge energy to earth, so it works only with a proper, low-resistance earth connection kept as short as possible. Without good earthing it gives little or no protection.
No. SPDs are designed for short transient surges from lightning and switching, not sustained overvoltage such as from a broken neutral or poor supply. For that, use a voltage protection relay, an over/under voltage protector or stabilisers for sensitive equipment.
Most SPDs have an indicator window that turns from green to red when the protective element has reached end of life. Pluggable SPDs allow replacing only the cartridge; check the indicator periodically and after major thunderstorms.
Yes, an SPD should have backup protection (MCB or fuse) as specified by the manufacturer, so a failed SPD can be safely disconnected without tripping the whole installation. The backup rating is usually listed in the SPD datasheet.
Imax is the maximum surge current it can discharge once, In is the nominal current it can handle repeatedly, and Up is the voltage protection level (the let-through voltage), where lower is better. For 230 V homes, a Type 2 SPD with Imax around 40kA and a maximum continuous operating voltage (Uc) of 275 V or more is commonly used.