Schneider Schneider EasyLogic PM1225H Energy Meter · 1P/3P · 1 A · Class 0.5 active energy · Class 0.5 re · IP51 · METSEPM1225HCL5 · METSEPM1225HCL5
Rated current1 A
Ingress protectionIP51 front:· IP30 body:
Reference standardIEC 61010-1:ed. 3
Net weight0.3 kg
BrandSchneider
Brand SKUMETSEPM1225HCL5
ELINEJRPJ3RRP9
Sold asPer pc
DepthOutside : 13 mm · Panel : 49 mm
ModelPM1225H
RangeEasyLogic
Width96 mm
SignalVoltage (impedance 5 MOhm)4 x · Current 0.005...10 A (impedance 0.3 MOhm)6 x
MaterialPolycarbonate
StandardsIEC 61010-1:ed. 3 · UL 61010-1:ed. 3
Display typeLCD display
Metering typeAverage current Iavg · Phase currents · Active power P, P1, P2, P3 · Active, reactive, apparent energy (signed, four quadrant) · Rotation speed · Average voltage Vavg · Calculated neutral current · Unbalance current · Apparent power S, S1, S2, S3 · Unbalance voltage · Frequency · Voltage U21, U32, U13, V1, V2, V3 · Demand power P, Q, S · Reactive power Q, Q1, Q2, Q3 · Power factor and displacement
Mounting modeFlush-mounted
Sampling rate32 samples/cycle
Accuracy classClass 0.5 active energy conforming to IEC 62053-21 · Class 0.5 reactive energy conforming to IEC 62053-24
Data recordingEnergy consumption logs
Display colourMonochrome
Display digits12 digit(s)
type of network3P · 2P + N · 1P + N · 3P + N · 2P
Demand intervals1 s
Flame retardanceV-0 conforming to UL 94
Local signallingGreen LED: activity · Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) · LED: voltage indication
Mounting supportFramework
Counter functionsON hour counting · ON-load hour counting · Power interruption
Network frequency50 Hz · 60 Hz
Tightening torqueCurrent circuit: 0.9…1 N.m Philips No 2 screwdriver · Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver · Control circuit: 0.9…1 N.m Philips No 2 screwdriver · Communication: 0.5…0.6 N.m Philips no 1 screwdriver
Device applicationEnergy monitoring
Provided equipmentInstallation guide
[In] rated current1 A · 5 A
Measurement current5…6000 mA
Measurement voltage46…277 V AC 50...60 Hz between phase and neutral · 80…480 V AC 50...60 Hz between phases · 277…999000 V AC 50...60 Hz with external VT
Type of measurementCurrent · Voltage · Frequency · Power factor · Phase angle · RPM · Peak demand power · Harmonic distortion (I THD & U THD) · Active power · Active energy
Measurement accuracyCurrent +/- 0.5 % · Voltage +/- 0.5 % · Frequency +/- 0.05 % · Power factor +/- 0.01 · Reactive power +/- 1 % · Active power +/- 1 % · Apparent power +/- 0.5 % · Active energy +/- 0.5 % · Reactive energy +/- 2 % · Apparent energy +/- 0.5 % · Harmonic distortion (I THD & U THD) +/- 5 %
Measurement categoryCategory III 480 V
Type of installationIndoor installation
Communication of dataReading of measurements · All counters · Revolution speed · Last cleared log · Instantaneous and demand values
Installation categoryIII
Wire stripping lengthCurrent circuit: 3.68 mm · Voltage circuit: 7 mm · Control circuit: 7 mm · 7 mm
Power quality analysistotal harmonic distortion
Product certificationsCE conforming to IEC 61010-1 · CULus conforming to UL 61010-1 · CULus conforming to CSA C22.2 No 61010-1 · C-Tick
Connections - terminalsCurrent circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s) · Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Communication: screw clamp terminals (bottom) 0.33…3.31 mm² cable(s)
Tamperproof of settingsProtected by access code
Product or component typeEnergy meter
[Us] rated supply voltage48...277 V AC/DC
Communication port supportScrew connector: RS485
Communication port protocolModbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
Electrical insulation classClass II
Frequency measurement range45…65 Hz
Maximum power consumption in W2 W at 36 V
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.