This Acti9 PRD1 is a modular surge arrester protecting 3P electrical installations against direct lightning strikes. The Imax maximum discharge current is 40kA .The In nominal discharge current is 25kA. The Type 1 surge arrester is recommended for electrical installations in the service sector and industrial buildings protected by a lightning conductor. It also provides type 2 protection and protect the electrical installation by finely clipping the lightning wave overvoltage. The surge arresters with "r" indication have remote transfer of the information "Cartridge to be replaced". The Uc maximum continuous operating voltage in common mode (between phase and earth) is 350VAC. The Up Voltage protection level in common mode (between phase and earth) is 1.5kV. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is anthracite grey (RAL7016).The dimensions are (W) 108mm x (H) 90mm x (D) 71mm. The weight is 1.010kg. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 80°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.
For most homes and apartments, a Type 2 SPD in the main DB is the standard choice. Type 1 or combined Type 1+2 is used at the service entrance of independent houses in lightning-prone areas or buildings with external lightning protection (SPDs are covered by IS 16463 (Part 11), identical to IEC 61643-11).
Yes. An SPD diverts surge energy to earth, so it works only with a proper, low-resistance earth connection kept as short as possible. Without good earthing it gives little or no protection.
No. SPDs are designed for short transient surges from lightning and switching, not sustained overvoltage such as from a broken neutral or poor supply. For that, use a voltage protection relay, an over/under voltage protector or stabilisers for sensitive equipment.
Most SPDs have an indicator window that turns from green to red when the protective element has reached end of life. Pluggable SPDs allow replacing only the cartridge; check the indicator periodically and after major thunderstorms.
Yes, an SPD should have backup protection (MCB or fuse) as specified by the manufacturer, so a failed SPD can be safely disconnected without tripping the whole installation. The backup rating is usually listed in the SPD datasheet.
The pole configuration of this SPD is 3P. A single-phase home typically uses a 1P+N or 2P SPD, and a three-phase supply uses 3P+N or 4P, so all live conductors are protected.
Imax is the maximum surge current it can discharge once, In is the nominal current it can handle repeatedly, and Up is the voltage protection level (the let-through voltage), where lower is better. For 230 V homes, a Type 2 SPD with Imax around 40kA and a maximum continuous operating voltage (Uc) of 275 V or more is commonly used.