This Resi9 product is a horizontal comb busbar 57 modules. It is dedicated to 3L installations. The type is L1L2L3 (Line). It is a set of 1 device. It is suitable for 19 devices (3P). The length is 1000mm. The total number of modules of 18mm is 57. The distance between each way is 54mm. The Ie rated operational current at 40°C is 63A. The Isc short circuit current is compatible with the breaking capacity of Schneider Electric circuit breakers. The Ui rated insulation voltage is 500VAC. The Ue rated operational voltage is 400VAC phase to phase. The colour of the device is white (RAL 9003).
Pin type busbars have pins that fit into the MCB's busbar terminal, while fork type busbars have forks that clamp under the terminal screw. Choose the type that matches the MCBs you are using.
Busbars are usually designed for a standard 18mm module pitch, but terminal depth and shape can vary between brands. Check compatibility with your MCB range before buying.
Copper has higher conductivity and is more compact for the same current, while aluminium is lighter and economical but needs larger cross-section and proper jointing. For DBs and panels, copper busbars are commonly preferred.
Blanking plates (blanking modules) cover unused ways so no one can touch live busbars through the gaps. They are an essential safety part and also keep dust and insects out of the DB.
Yes, when a DB has more than one RCCB, each RCCB must have its own neutral link so that neutrals of its circuits do not mix with others. Mixing neutrals causes nuisance tripping.