This Harmony RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24V DC, 24V to 240V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. Multi function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC.
An on-delay timer switches its output after the set time once it receives power or a start signal, while an off-delay timer holds its output on for the set time after the signal is removed. Multifunction timers offer both and other modes such as cyclic and interval.
A dedicated star-delta timer has a built-in short dead time between star and delta changeover to prevent a short circuit across contactors. The star time is set to suit how fast the motor reaches near full speed, often a few seconds to around 15 seconds.
A phase monitoring relay detects phase loss, phase reversal (wrong sequence) and often phase unbalance or under/over voltage, and trips the contactor coil to protect three-phase motors. It is especially useful for pumps, compressors and lifts where wrong rotation or single phasing can cause damage.
A cyclic or programmable timer can switch a pump contactor on and off at set intervals, but for tank level control a level controller relay with probes or a float switch is more reliable. The pump also needs proper motor protection like an MPCB or overload relay.
Most modern timers and monitoring relays are DIN rail mounted (35mm), while some older or plug-in types use an 8-pin or 11-pin socket base. Check the mounting type and whether the base is included.