Schneider Schneider EcoStruxure PAS400 Gateway · EcoStruxure Panel Server · entry wireless · PAS400
Ingress protectionIP40 (front face)
Reference standardIEC 61010
Net weight0.163 kg
BrandSchneider
Brand SKUPAS400
ELINEFMJKR7MM4
Sold asPer pc
Depth70.2 mm
RangeEcoStruxure
Width54 mm
Height93 mm
StandardsIEC 61010 · IEC 61010-1 · IEC 61010-2-201 · UL 61010 · UL 61010-1 · UL 61010-2-201 · EN 61010-1 · EN 61010-2-201 · CAN/CSA C22.2 No. 61010-1-12 · CAN/CSA C22.2 No. 61010-2-201 · IEC 62974-1 · IEC 61326-1 · EN 61326-1 · ETSI EN 301 489-1 · ETSI EN 301 489-17 · EN 301-893 · EN 55032 · CISPR 11 · ETSI EN 300 328 · IEEE 802.15.4 · IEEE 802.11a/b/g/n · IEEE 802.3 af/at · FCC CFR 47 part 15 class A · EN
Product namePanel Server Entry
Web servicesHTTPS server · SFTP publication (CSV / JSON) · HTTPS publication (CSV / JSON)
Mounting modeClip-on
Data recordingReal time data monitoring
Realtime clockWith RTC-battery set · With user calibration
Memory capacity512 MB NAND
Mounting supportDIN rail
Number of inputs0
Pollution degree2
Device short namePAS400
Number of devices64 Modbus TCP/IP
Relative humidity5…95 %
Tightening torquePower supply: 0.6 N.m · Communication: 0.25 N.m
Device applicationGateway
Function availableEmbedded web page for configuration and upgrade · Diagnosis capabilities · Diagnostic report · Diagnostics on communication · Energy management · With integrated web server · Firmware update · Backup/restore configuration · Configurable event
Operating altitude< 2000 m
Range compatibilityEcoStruxure Facility Expert · EcoStruxure Building Operation · EcoStruxure Power Operation · EcoStruxure Power Monitoring Expert · EcoStruxure Asset Advisor · EcoStruxure Energy Hub · EcoStruxure Resource Advisor · Third party SCADA
Communication gatewayEthernet TCP/IP to wireless devices
Communication serviceDevice Profile for Web Services (DPWS) · Modbus TCP server · SNTP client · DHCP client · RSTP
Product compatibilityWireless access point
Wire stripping lengthPower supply: 7 mm · Communication: 7 mm
Product certificationsCE · cULus · CB · RCM · UKCA · FCC · IC · DNV Marine · ANSI RF · IACS E10
Commissioning interfaceEcoStruxure Power Commission desktop · EcoStruxure Power Commission Mobile (through Wi-Fi Access point) · Web page
Connections - terminalsPower supply: screw terminal block (top) 1.5…2.5 mm² cable(s) · Communication: screw terminal block (bottom) 0.14…1.5 mm² cable(s)
IP degree of protectionIP40 (front face) · IP20 (casing)
Communication iinterfaceWireless (IEEE802.15.4) product
Product or component typeGateway
[Us] rated supply voltage110...277 V AC 50/60 Hz
Communication network typeEthernet 10/100BASE-T · Wi-Fi infrastructure2.4 GHz · Wi-Fi infrastructure5 GHz · Wi-Fi access point2.4 GHz · Wireless IEEE 802.15.4
Communication port support1 RJ45: ETHERNET
Number of server device(s)20 wireless (IEEE 802.15.4) product(s) - mixed
Communication port protocolModbus TCP · DHCP · HTTPS · NTP/SNTP · IPv4 · IPv6 · TCP/IP
Product specific applicationWireless Schneider Electric devices ecosystem
Time synchronisation protocolNTP · SNTP
Maximum power consumption in W3.5 W 110...277 V
Maximum power consumption in VA12 VA at 110...277 V
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-25…60 °C
Data buffer for data publication (cloud, SFTP, HTTPS) depending on network1 month(s)
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.