This Acti9 iSSW is a linear switch used for the manual control of electric circuits. It is a 3 positions switch with 2 changeover contacts (2 C/O). The phase-separated wall can be divided to allow all the types of com busbar to pass through. It comes with staggered terminals to simplify connection. The tightening torque of connection is 1N.m for PZ1 screwdriver type. The Ue rated operational voltage is 250VAC. The Ie rated operational current is 20A. The operating frequency is 50Hz. The connection allows rigid copper cables from 0.5mm² minimum to 2x2.5mm² maximum. The connection allows flexible or with ferrule copper cables from 0.5mm2 minimum to 2x2.5mm² maximum. The number of cycles open and close (O-C) is 30000. The endurance is 30000 operations with AC22 current category under cos phi=0.8. The width in 9mm pitches is 4. The dimensions are (W) 36mm x (H) 82mm x (D) 75mm. The pollution degree is 3. The tropicalization is treatment 2 (relative humidity 95% at 55°C). The operational temperature is from -20°C to +50°C. The storage temperature is from -40°C to +70°C. It complies with IEC 60669-1 and IEC 60947-5-1 standards.
Use a changeover switch rated at least equal to your main incomer, with poles matching the supply (2 pole for single-phase, 4 pole for three-phase) so the neutral is also switched. This prevents generator power feeding back into the grid, which is dangerous for line workers, and installation should be done by a licensed electrician.
An on-load changeover switch is designed to transfer between mains and generator while current is flowing, while an off-load type must only be operated after the load is switched off. On-load types are safer and more convenient for most homes and shops; check the load rating on the product.
A manual changeover needs someone to operate the handle when power fails, while an ATS (automatic transfer switch) senses mains failure and switches to the generator automatically, often also starting the DG set. ATS is used where unattended or quick changeover is needed.
The centre OFF position ensures the load is fully disconnected from both sources before connecting to the other, so mains and generator can never be connected together. It is also used to isolate the load safely for maintenance.
Yes, a changeover switch is often used to select between inverter output and mains, or to bypass the inverter during servicing. Size it for the circuits it will carry and make sure inverter output and mains are never paralleled.