TeSys GV electrical trip, MN undervoltage release, 110-115V AC 50Hz / 127V AC 60Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
An MPCB has an adjustable overload setting matched to the motor's current and a magnetic trip set to handle motor starting current, plus phase loss sensitivity. An MCB has fixed overload settings meant for cables, so it does not protect a motor as precisely (MPCBs are covered by IS/IEC 60947-2 and 60947-4-1).
Yes, an MPCB gives short-circuit and overload protection plus isolation in one device, so with a contactor it forms a compact DOL starter without a separate overload relay or fuses. Check the manufacturer's coordination table for the right contactor pairing.
Yes, an MPCB can be used as a manual motor starter for occasional on/off switching. For frequent starts, remote control or float/pressure switch operation, pair it with a contactor.
Common accessories include auxiliary contacts, trip-indication contacts, undervoltage and shunt releases, enclosures for wall mounting and connection links to contactors. These are usually specific to the MPCB range.
Check that the dial is set to the motor's full-load current, that all three phases are present and balanced, and that the pump or load is not jammed. If the motor current is near the top of the range, the next range up may be needed; consult an electrician before increasing settings.