Schneider Schneider EasyLogic EM6459H VAF PF Meter · CONZERV EM6459H VAF PF DPM RS485 CL 0.5 · METSEEM6459HCL05RS · METSEEM6459HCL05RS
Rated current1 A
Ingress protectionIP51 front:· IP30 body:
Reference standardIEC 61010-1:ed. 3
Net weight0.3 kg
BrandSchneider
Brand SKUMETSEEM6459HCL05RS
ELINEF3KH4C7CH
Sold asPer pc
RangeEasyLogic
SignalVoltage (impedance 5 MOhm)4 x · Current 0.005...10 A (impedance 0.3 MOhm)6 x
MaterialPolycarbonate
StandardsIEC 61010-1:ed. 3 · UL 61010-1:ed. 3
fixing modeBy clamp
Display type7 segments LED
Product nameEasyLogic EM64XXH RS
Metering typePhase currents · Average voltage Vavg · Average current Iavg · Unbalance current · Calculated neutral current · Rotation speed · Voltage U21, U32, U13, V1, V2, V3 · Percentage of load · Power factor and displacement PF (signed, four quadrant) · Unbalance voltage · Frequency
Mounting modeFlush-mounted
Sampling rate32 samples/cycle
Display colourRed
Display digits12 digit(s) - 14.2 mm in height
type of network3P + N · 1P + N · 2P · 3P · 2P + N
Demand intervals1 s
Flame retardanceV-0 conforming to UL 94
Local signallingGreen LED: activity · Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Mounting supportFramework
Counter functionsPower interruption · ON hour counting · Power outage counting
Device short nameEM6459H
Network frequency50 Hz · 60 Hz
Number of outputs0
Tightening torqueCurrent circuit: 0.9…1 N.m Philips No 2 screwdriver · Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver · Control circuit: 0.9…1 N.m Philips No 2 screwdriver · Communication: 0.5…0.6 N.m Philips No 2 screwdriver
Device applicationPower factor control · Load control · Power monitoring
Provided equipmentInstallation guide
[In] rated current1 A · 5 A
Measurement current5…6000 mA
Measurement voltage46…277 V AC 50...60 Hz between phase and neutral · 80…480 V AC 50...60 Hz between phases · 277…999000 V AC 50...60 Hz with external VT
Type of measurementCurrent · Voltage · Frequency · Power factor · RPM
Measurement accuracyCurrent +/- 0.5 % · Voltage +/- 0.5 % · Frequency +/- 0.05 % · Power factor +/- 0.01
Measurement categoryCategory III 35…480 V
Type of installationIndoor installation
Communication of dataReading of measurements · Revolution speed · All counters · Percentage of load
Installation categoryIII
Wire stripping lengthCurrent circuit: 3.68 mm · Voltage circuit: 7 mm · Control circuit: 7 mm · Communication: 7 mm
Connections - terminalsCurrent circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s) · Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) · Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
Tamperproof of settingsProtected by access code
Messages display capacity3 fields of 4 characters
Product or component typeVAF PF meter
[Us] rated supply voltage44...277 V AC 45...65 Hz · 44...277 V DC
Communication port supportScrew terminal block: RS485
Communication port protocolModbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
Electrical insulation classClass II
Frequency measurement range45…65 Hz
Maximum power consumption in W2 W at 240 V
Maximum power consumption in VA4 VA at 240 V between phase and neutral
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.