The Allzy range CAT number 681257 is a 10A Modular MCB SP 1M designed for overload and short circuit protection. It features a single pole with C curve characteristics, available in white and matt black colors, and can be flush or surface-mounted. The MCB has overall dimensions of 22.5 mm width, 45 mm height, and 41 mm depth, weighing 58 grams. It includes screw terminals with a capacity of 1.5mm² to 6mm², operable with a 4mm to 5mm flat-blade screwdriver. The switch operates with a dolly (knob) and is constructed with materials such as nylon with 30% glass field for the dolly, PBT for the bottom and top covers, polycarbonate for the top plate, and brass with silver plating for the screws and terminals. Electrically, it operates at 240V AC with a current rating of 10A and a short circuit capacity of 1.5KA. Markings include rating, voltage, short circuit capacity, ON-OFF indication, connection diagram, manufacturing country, traceability, and ISI marking, conforming to IS: 60898-1:2002 standards.
Many 1.5 ton split ACs are put on a dedicated 16A or 20A MCB (C curve is common) with 2.5 or 4 sq mm copper wire, depending on the rated current on the nameplate and the cable run. Follow the AC's installation manual and have a licensed electrician size the MCB to protect the cable, not just the appliance.
The curve sets how fast the MCB trips on a surge: B trips at 3-5 times rated current, C at 5-10 times and D at 10-20 times (IS/IEC 60898-1). B suits lighting and resistive loads, C is the usual choice for homes with ACs, fans, motors and pumps, and D is for high inrush loads like transformers and large motors.
A DP (double pole) MCB switches off both phase and neutral, giving full isolation for high-load or wet-area appliances like geysers, ACs and the main incomer. SP MCBs are fine for normal lighting and socket circuits where only the phase needs protection.
Breaking capacity is the maximum fault current the MCB can safely interrupt; 6kA is adequate for most homes and 10kA is recommended near large transformers, in commercial buildings or industrial sites where prospective fault current is higher. Choosing 10kA does not change how the MCB behaves on normal overloads.
Most modular MCBs mount on a standard 35mm DIN rail and are one module (about 18mm) wide per pole, so they usually physically fit. The front cover cutout height and busbar terminal type can differ between brands, so check the cover alignment before mixing brands in one DB.
No. An MCB protects wiring against overload and short circuit only; protection against shock and earth leakage needs an RCCB or RCBO (typically 30mA) in the same circuit.