This Acti9 xSW is a modular and reliable switch disconnector. it is a 4 poles, rated current is 125A, and o poleserating voltage is 415VAC. Electrical endurance goes up to 30000 cycles, and Mechanical endurance goes up to 300000 cycles. The operating temperature is -20°C to +50°C. The storage temperature is -40°C to +70°C. The degree of protection is IP20 and IP40 in an enclosure. It is DIN rail mountable. Total number of 18 mm modules 4. This switch disconnector is used for control. This product is compliant with EN/IEC 60669-1,EN/IEC 60947-3.
An isolator (switch-disconnector) only switches the circuit on and off and does not trip on overload or short circuit, while an MCB provides protection. Isolators are used as main switches in DBs or near equipment for safe maintenance, and must be backed by a suitable MCB, MCCB or fuse.
Yes, a DP isolator for single-phase or 4P isolator for three-phase is commonly used as the DB incomer, provided protection is given upstream (by the meter-side fuse or MCB) and on each outgoing circuit. Its current rating should be equal to or higher than the upstream protection rating.
Switch-disconnectors to IS/IEC 60947-3 are rated for switching under load according to their utilisation category, such as AC-22 for mixed resistive and inductive loads or AC-23 for motor loads. Check the category on the product before using it to switch motors directly.
Use 2 pole for single-phase supply (phase and neutral) and 4 pole for three-phase supply with neutral, so all live conductors are disconnected during maintenance. A 3 pole isolator is used where no neutral is switched, such as some motor feeders.
Many isolators and rotary switch-disconnectors have a padlocking provision in the OFF position so no one can switch them on while work is in progress. Check for the lock-off feature if it is needed for your site's safety procedures.