This Acti9 product is a surface or flush mounted 4 ways phase segregated distribution board. It allows the mounting of modular devices on 36 modules of 18mm such as MCBs (4P and 1P), isolator (4P), RCCB (2P), and RCBO (2P). This distribution board comes with a reversible split metal door for door opening. The In rated current is 63A. It is provided with removable gland plates, removable centre plates, removable frame, grounding bar, neutral bar, busbar, cable, and rotary lock. The dimensions are (W) 506mm x (H) 607.2mm x (D) 98.6mm. The colour of the distribution board is white (RAL 9003). The weight is 14.25kg. The box, cable gland plate, and DIN rail are made of galvanized steel and CRCA is for the door, frame, and centre plate. The IP degree of protection is IP43 and IK09 with the split metal door. This distribution board complies with IS 8623-1 and 3, and IEC 61439-3 standards. It is certified with NABL certification.
SPN stands for Single Pole and Neutral, a DB for single-phase supply with a phase busbar, a neutral link and an earth bar. It is the standard DB for most Indian homes and small shops with single-phase connections.
Count one way per circuit (lighting, sockets, each AC, geyser, kitchen, etc.) plus incomer space, then add about 20-30% spare for future loads. A typical 2BHK uses around 8-12 ways and a 3BHK around 12-16 ways, but your circuit plan decides it.
Most SPN DBs have incomer space for a DP MCB or isolator plus a 2-module RCCB, but this depends on the board. Check the incomer configuration, or choose an RCCB-ready DB if you want shock protection for all circuits.
Flush (concealed) DBs are recessed into the wall and suit new construction or renovation, while surface-mounted DBs are fixed on the wall and easier to retrofit. Measure the wall depth before choosing a flush DB.
Most distribution boards are sold empty with busbar, neutral link and earth bar, and MCBs are bought separately. Check the package contents on the product page.