This Acti9 xC60 is a low voltage biconnect miniature circuit breaker (MCB). It is a 4P circuit breaker with 4 protected poles and 63A In rated current with B tripping curve. The rated short circuit breaking capacity is up to 10 kA at 415VAC conforming to IS/IEC 60947-2 standard. The MCB is suitable for isolation in the industrial sector as per IS/IEC 60947-2. This miniature circuit breaker protects circuit against short circuit and overload current. The presence of the green strip guarantees physical opening of the contacts. It allows operations to be performed on the downstream circuit in complete safety. Mechanical durability goes up to 20000 cycles and electrical durability goes up to 10000 cycles. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The operating frequency is 50Hz or 60Hz. It can be mounted on DIN rail for modular installation. Its width is 8 pitches of 9mm. Pollution degree is 3. The product colour is white (RAL9003) According to IEC 60529 standard, the degree of protection is IP20 for the device The operating temperature is -30°C to 70°C. The storage temperature is -40°C to 85°C. .
Many 1.5 ton split ACs are put on a dedicated 16A or 20A MCB (C curve is common) with 2.5 or 4 sq mm copper wire, depending on the rated current on the nameplate and the cable run. Follow the AC's installation manual and have a licensed electrician size the MCB to protect the cable, not just the appliance.
The curve sets how fast the MCB trips on a surge: B trips at 3-5 times rated current, C at 5-10 times and D at 10-20 times (IS/IEC 60898-1). B suits lighting and resistive loads, C is the usual choice for homes with ACs, fans, motors and pumps, and D is for high inrush loads like transformers and large motors.
A DP (double pole) MCB switches off both phase and neutral, giving full isolation for high-load or wet-area appliances like geysers, ACs and the main incomer. SP MCBs are fine for normal lighting and socket circuits where only the phase needs protection.
Breaking capacity is the maximum fault current the MCB can safely interrupt; 6kA is adequate for most homes and 10kA is recommended near large transformers, in commercial buildings or industrial sites where prospective fault current is higher. Choosing 10kA does not change how the MCB behaves on normal overloads.
Most modular MCBs mount on a standard 35mm DIN rail and are one module (about 18mm) wide per pole, so they usually physically fit. The front cover cutout height and busbar terminal type can differ between brands, so check the cover alignment before mixing brands in one DB.
No. An MCB protects wiring against overload and short circuit only; protection against shock and earth leakage needs an RCCB or RCBO (typically 30mA) in the same circuit.