Schneider Schneider TeSys Deca GV2ME Motor Protection Circuit Breaker · 3P · 13-18 A · 100 kA · GV2ME20 · GV2ME20
Poles3P
Rated current18 A
Breaking capacity100 kA
Ingress protectionIP20
Reference standardEN/IEC 60947-2
ColourDark grey
Net weight0.26 kg
BrandSchneider
Brand SKUGV2ME20
ELINE44MFH9P2H
Sold asPer pc
Depth78.5 mm
RangeTeSys Deca
Width45 mm
Height89 mm
StandardsEN/IEC 60947-2 · EN/IEC 60947-4-1 · UL 60947-4-1 · CSA C22.2 No 60947-4-1 · IEC/EN 60335-2-40:Annex JJ · IEC/EN 60335-1:Clause 30.2
Rated dutyUninterrupted conforming to IEC 60947-4-1
Fixing mode35 mm symmetrical DIN rail: clipped · Panel: screwed (with adaptor plate)
Control typePush-button
Network typeAC
Product nameTeSys GV2
Motor power kW7.5 kW at 400/415 V AC 50/60 Hz · 9 kW at 500 V AC 50/60 Hz · 15 kW at 690 V AC 50/60 Hz
Fire resistance960 °C conforming to IEC 60695-2-11
Device short nameGV2ME
Mounting positionHorizontal · Vertical
Network frequency50/60 Hz conforming to IEC 60947-2
Poles description3P
Tightening torque1.7 N.m - on screw clamp terminal
Climatic withstandconforming to IACS E10
Device applicationMotor protection
[In] rated current18 A
Trip unit technologyThermal-magnetic
Utilisation categoryCategory A conforming to IEC 60947-2 · AC-3 conforming to IEC 60947-4-1 · AC-3e conforming to IEC 60947-4-1
Electrical durability100000 cycles for AC-3 at 415 V In · 100000 cycles for AC-3e at 415 V In
Mechanical durability100000 cycles
Mechanical robustnessShocks: 30 Gn for 11 ms · Vibrations: 5 Gn, 5...150 Hz
Product certificationsCB Scheme · CE · UKCA · CCC · cULus · EAC · ATEX · LROS (Lloyds register of shipping) · BV · RINA · DNV-GL
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid · Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end · Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
IK degree of protectionIK04
IP degree of protectionIP20 conforming to IEC 60529
Magnetic tripping current341 A
Phase failure sensitivityYes conforming to IEC 60947-4-1
Product or component typeMotor circuit breaker
Suitability for isolationYes conforming to IEC 60947-1
Power dissipation per pole2.5 W
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Ambient air temperature for storage-40…80 °C
Thermal protection adjustment range13…18 A conforming to IEC 60947-2
Ambient air temperature for operation-20…60 °C
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
[Ith] conventional free air thermal current18 A conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 · 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 · 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.