Siemens Sentron 3WT8 ACB 2000 A (article 3WT8202-6UA34-5AB2) is a air circuit breaker (acb) from Siemens, 3WT8 series, sold by Elume with a GST invoice and pan-India delivery. Key data: manufacturer product name withdrawable circuit breaker 3-pole, size 2 In=2000A to 500V, 50/60Hz AC Icu=66kA at 500V with mechanical lockout device with tripped signaling switch with tripped indicators with guide frame Overcurrent release ETU37WT LSING Setting range according to FS with display Motorized/manual operating mechanism with memory with electrical and mechanical activation Motor and electr. calling for 220...240 V AC, 220...250 V DC Activation solenoid 220...250 V DC without 1st auxiliary release With 2nd auxiliary release Shunt release "F", F2 220...240 V AC, 220...250 V DC switch position-depending Auxiliary current switch 2 NC+2 NO 2-piece shutter with sealing cap against unauthorized switching off with door sealing frame, ampere/current rating 2000 A, breaking capacity icu 66 kA, no. of poles 3 Pole, tripping type Electronic / Microprocessor, protection type O/L S/C & E/F, operating type Electrical Draw Out, rated voltage (v) 500V AC. Priced at the Siemens India list price of 2026 (MRP before GST Rs 12,76,025), GST included in the price shown.
ACBs are used for very high currents, typically 630A up to 6300A, mostly as transformer or main LT panel incomers and bus couplers. They offer high short-time withstand (Icw), advanced releases and maintainability that MCCBs usually do not; both are covered by IS/IEC 60947-2.
A fixed ACB is bolted directly into the panel, while a draw-out ACB sits in a cradle and can be racked out for testing or maintenance without disturbing the busbars. Draw-out is preferred for main incomers and critical supplies where quick replacement and safe isolation matter.
MDO (manually operated draw-out) is closed and opened by hand, while EDO (electrically operated draw-out) has a motor and closing/shunt coils for remote operation, auto changeover with DG sets and synchronising schemes. Choose EDO if the ACB will be part of an automatic transfer or SCADA/BMS system.
As a rule of thumb, the incomer ACB is rated slightly above the transformer's full-load LT current (about 1.39A per kVA at 415V, so a 1000 kVA transformer needs roughly 1400A, usually a 1600A ACB). The breaking capacity must also exceed the transformer's LT fault level; a qualified electrical engineer should confirm the selection.
Yes. ACBs need periodic inspection of contacts, arc chutes, mechanism lubrication and release testing as per the manufacturer's maintenance schedule, typically at least once a year or after a major fault trip. Maintenance should only be done by trained personnel with the ACB racked out and isolated.