Schneider Schneider PowerLogic PowerTag R200 Energy Sensor · Class 1 active energy · Class 2 reactive energy · A9MEM1590 · A9MEM1590
Ingress protectionIP20
Reference standardIEC 61557-12
ColourWhite (RAL 9003)
BrandSchneider
Brand SKUA9MEM1590
ELINE43J4KH6FF
Sold asPer pc
DepthBase unit: 67.5 mm
Poles3P · 3P + N
WidthBase unit: 18 mm
HeightBase unit: 105 mm
StandardsIEC 61557-12 · IEC 61010-1 · ETSI EN 301 489-1 · IEC 61010-2-030 · IEC 61326-1 · ETSI EN 300 328
Directives2014/53/EU - radio equipment directive
Form factorRope
Cable length1 m for sensor
Product namePowerTag R200
Metering typeActive energy E -a- IN/OUT 0...281 x 10exp(9) kWh at total per phase · Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at partial per phase · Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase total · Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase partial · Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at total per phase · Reactive energy E -rA- IN/OUT 0...281 x
Mounting modeClip-on (DIN rail)
Accuracy classClass 1 active energy conforming to IEC 61557-12 · Class 2 reactive energy conforming to IEC 61557-12 · Class 2 apparent energy conforming to IEC 61557-12 · Class 1 active power conforming to IEC 61557-12 · Class 2 reactive power conforming to IEC 61557-12 · Class 2 apparent power conforming to IEC 61557-12 · Class 1 current conforming to IEC 61557-12 · Class 0.5 voltage conforming to IEC 61557-12
Emission power10 mW
Quality labelsCE
supply voltage100...277 V AC, +/- 20 %, phase to neutral · 173...480 V AC, +/- 20 %, phase to phase
Event managementVoltage loss with measured current at voltage loss
Mounting supportBusbar · Cables
Range of productPowerLogic
Starting current120 mA
Mounting locationTop or bottom
Network frequency50 Hz · 60 Hz
Operating altitude0...2000 m
Saturation current400 A
[Ib] Basic current30 A
Cable cross section1 rigid cable 0.2…1.5 mm² without cable end · 1 stranded cable 0.2…2.5 mm² without cable end · 1 stranded cable 0.25…1.5 mm² with cable end
Product destinationSwitchboard
Range compatibilityMasterpact MasterPact MTZ for switch disconnector · Masterpact MasterPact NW · Masterpact MasterPact NT · Compact NS Compact NS100 · Acti9 · TeSys
Type of measurementActive and reactive energy · Apparent energy · Active and reactive power · Apparent power · Current · Voltage · Power factor · Internal temperature · Frequency
Measurement categoryCategory IV conforming to IEC 61010-2-030
Overvoltage categoryIV conforming to IEC 61010-1
Wire stripping length11 mm
Maximum current [Imax]200 A
Product certificationsUL listed · IEC · DNV Marine
current sensor diameterClosed: 100 mm
Maximum power consumption3 VA
Product or component typeEnergy sensor
Concentrator compatibilityEcoStruxure Panel Server Entry · EcoStruxure Panel Server Universal · EcoStruxure Panel Server Advanced · PowerLogic T300 · Harmony Hub · Acti9 PowerTag Link · Acti9 PowerTag Link HD
Transmission support mediumRadio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4
Product specific applicationEnergy management · Overload alarm · Power factor · Load monitoring · Circuit monitoring
Maximum conductor temperature105 °C
Number of 9mm pitches on Din rail2
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-25…70 °C
Electrical connection (voltage sensing & power supply)Removable spring terminal block
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.