This Acti9 iPRD8 surge arrester protects 1P+N installations. It allows quick replacement of damaged cartridges. The Imax maximum discharge current is 8kA .The In nominal discharge current is 2.5kA. The iPRD8r ensures secondary protection of loads to be protected and is placed in cascade with the incoming surge arresters. This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in diiferential mode (between phase and neutral) is 350VAC. The Up Voltage protection level in common mode is 1.4kV between neutral and earth in type 2, and 1.1kV between neutral and earth in type 3. The Up Voltage protection level in differential mode (between phase and neutral) is 1kV in type 2, and 1.1kV in type 3. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 211g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperatu
For most homes and apartments, a Type 2 SPD in the main DB is the standard choice. Type 1 or combined Type 1+2 is used at the service entrance of independent houses in lightning-prone areas or buildings with external lightning protection (SPDs are covered by IS 16463 (Part 11), identical to IEC 61643-11).
Yes. An SPD diverts surge energy to earth, so it works only with a proper, low-resistance earth connection kept as short as possible. Without good earthing it gives little or no protection.
No. SPDs are designed for short transient surges from lightning and switching, not sustained overvoltage such as from a broken neutral or poor supply. For that, use a voltage protection relay, an over/under voltage protector or stabilisers for sensitive equipment.
Most SPDs have an indicator window that turns from green to red when the protective element has reached end of life. Pluggable SPDs allow replacing only the cartridge; check the indicator periodically and after major thunderstorms.
Yes, an SPD should have backup protection (MCB or fuse) as specified by the manufacturer, so a failed SPD can be safely disconnected without tripping the whole installation. The backup rating is usually listed in the SPD datasheet.
The pole configuration of this SPD is 1P+N. A single-phase home typically uses a 1P+N or 2P SPD, and a three-phase supply uses 3P+N or 4P, so all live conductors are protected.
Imax is the maximum surge current it can discharge once, In is the nominal current it can handle repeatedly, and Up is the voltage protection level (the let-through voltage), where lower is better. For 230 V homes, a Type 2 SPD with Imax around 40kA and a maximum continuous operating voltage (Uc) of 275 V or more is commonly used.