This Acti9 DPN N Vigi is a residual current device. It is a 1P+N circuit breaker and rated current is 6A. The earth leakage protection class is A-SI type with a sensitivity of 30mA and a voltage independent technology. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. The DPN Vigi residual current device provides complete protection for final circuits against overcurrents and insulation faults. This product provides complete protection for people against electric shocks by direct contacts (30 mA), This product is compliant with EN 61009-1 and IEC 61009-1 standard. Electrical endurance goes up to 20000 cycles. Mechanical endurance goes up to 20000 cycles. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The pollution degree is 3. It can be mounted on DIN rail. The width in 9mm pitches is 4. The product color is white (RAL9003). The weight is 0.19kg. The degree of protection is IP20 and IP40 in an enclosure. The operating temperature -25°C to +60°C. The storage temperature is -40°C to +60°C.
An RCBO combines an MCB and an RCCB in one device, protecting a single circuit against overload, short circuit and earth leakage. An RCCB only handles earth leakage and needs separate MCBs (RCBOs are covered by IS 12640 (Part 2)).
With RCBOs, a leakage fault on one circuit trips only that circuit, so the rest of the house keeps power and it is easier to find the fault. They cost more and take more DB space than one RCCB with several MCBs, so many homes use RCBOs only on critical circuits like geyser, washing machine and outdoor points.
This RCBO trips on leakage at 30 mA, in addition to normal overload and short-circuit protection. 30mA is the usual choice for shock protection on final circuits.
Yes, an RCBO suits geysers, pumps and other loads in wet areas because it gives shock protection and overload protection on that one circuit. Choose the current rating and curve as you would for an MCB, based on the appliance's rated current and the cable, and have a licensed electrician confirm.
Yes. The RCBO compares phase and neutral current to detect leakage, so the circuit's neutral must pass through it and must not be shared with any other circuit.
RCBOs mount on the standard 35mm DIN rail, but many are 2 modules wide or need a separate neutral connection, so check that your DB has enough free ways and space. Some compact single-module RCBOs fit like an SP MCB; refer to the product's module width.