ABB E 92/50 Fuse disconnector · 2CSM277972R18012CSM277972R1801↓ 4% off MRP
BrandABB
CategorySwitchgear
SpecificationE 90 50/125 fuse holders are appropriate to protect against overloads and short circuits. They are designed for use with cylindrical fuses from 50 to 125 A.
Brand SKU2CSM277972R1801
AvailabilityIn stock · ships in 24h
DeliveryPan-India · 7 working days
ABB· In stock
Visit the ABB store

ABB E 92/50 Fuse disconnector · 2CSM277972R1801

₹3,431/pcincl. GST-4%
₹2,908 + 18% GST · MRP ₹3,574
Add to cart
Buy now
  • Secured by Razorpay · UPI, cards, net banking, wallets
  • GST invoice, claim input tax credit
  • Tracked delivery, 5 to 7 working days
✓ Full brand warranty on every order
✓Lowest price guarantee · found it cheaper? We match it.
💳 30 Day credit facility available launching soon - join waitlist.
₹3,431 /pc incl. GST
Free delivery over ₹4,000

ABB E 92/50 Fuse disconnector · 2CSM277972R1801: Elume price today ₹3,431 per pc incl. GST, 4% below the ₹3,574 MRP. The price has held steady for the last 30 days. The average price across the sellers we track is ₹2,745, ₹686 less than here.

Price history
Elume price vs the average market price across the sellers we track, day by day. Tap a legend entry to show or hide a line.
25 May to 22 Nov
₹3,824₹3,489₹3,153₹2,818₹2,482₹3,574₹3,431₹2,745
May 26Jun 26Aug 26Sep 26Oct 26Nov 26Nov 26
Elume today
₹3,431
Avg market price
₹2,745
MRP
₹3,574
Lowest in view · 10 Aug
₹2,669
Highest in view · 3 Oct
₹3,574
🏷️
100% genuine
Brand-authorised stock with full manufacturer warranty
🧾
GST invoice
Tax invoice on every order · GST billing with tax split
🚚
Pan-India delivery
7 working days to your location
📦
Wholesale built in
Wholesale price at 15+ units: ₹3,259/pc on this product, applied automatically

E 90 50/125 fuse holders are appropriate to protect against overloads and short circuits. They are designed for use with cylindrical fuses from 50 to 125 A.

As published by ABB. Verify critical parameters against the datasheet before specifying.
ABB ABB E 92/50 Fuse disconnector · 2CSM277972R1801 · 2CSM277972R1801
Device typeIsolator (switch disconnector)
Poles2P (DP)
Rated current125 A
Rated voltageAC-20B 690 V
Frequency50/60 Hz
Insulation voltage (Ui)1 kV
Width3 modules (53.4 mm)
Terminal capacityRigid 2.5 ... 35 mm²
Ingress protectionIP20
Net weight0.19 kg
Current rating125 A
Reference standardIEC 60947-3
BrandABB
Brand SKU2CSM277972R1801
ELINEGM4J47H7D
Sold asPer pc
Ratings as published by ABB (abb.com product data, datasheet 2CSC444002B0204; Product name). Verify critical parameters against the datasheet before specifying.
Read: Contactor Sizing for 400 V and 415 V Motors: kW to Amps, AC-3 Ratings and Overload Relays →
What size contactor do I need for a 7.5 kW motor?
A 7.5 kW three-phase motor at 400 V draws about 14.5 A, so a contactor rated at least 16 to 18 A at AC-3 is the usual choice, with an overload relay set to the nameplate current.
What is the difference between AC-1 and AC-3?
AC-1 is the rating for resistive loads such as heaters; AC-3 is the rating for switching squirrel-cage motors in normal duty. Motors are always sized on the AC-3 figure, which is lower.
How many amps per kW for a three-phase motor?
At 400 V, roughly 2 A per kW for small motors, falling towards about 1.8 A per kW above 30 kW, because larger motors run at a better power factor and efficiency. Use the nameplate for the exact figure.
What is the difference between an isolator and an MCB?

An isolator (switch-disconnector) only switches the circuit on and off and does not trip on overload or short circuit, while an MCB provides protection. Isolators are used as main switches in DBs or near equipment for safe maintenance, and must be backed by a suitable MCB, MCCB or fuse.

Can I use an isolator as the main switch in my DB?

Yes, a DP isolator for single-phase or 4P isolator for three-phase is commonly used as the DB incomer, provided protection is given upstream (by the meter-side fuse or MCB) and on each outgoing circuit. Its current rating should be equal to or higher than the upstream protection rating.

Is this isolator safe to switch on load?

Switch-disconnectors to IS/IEC 60947-3 are rated for switching under load according to their utilisation category, such as AC-22 for mixed resistive and inductive loads or AC-23 for motor loads. Check the category on the product before using it to switch motors directly.

2 pole or 4 pole isolator - which one do I need?

Use 2 pole for single-phase supply (phase and neutral) and 4 pole for three-phase supply with neutral, so all live conductors are disconnected during maintenance. A 3 pole isolator is used where no neutral is switched, such as some motor feeders.

Can an isolator be locked off for maintenance?

Many isolators and rotary switch-disconnectors have a padlocking provision in the OFF position so no one can switch them on while work is in progress. Check for the lock-off feature if it is needed for your site's safety procedures.

No reviews yet