ABB CM-MSS.23P Therm. motor protec. relay 2c/o, 110-130VAC/220-240VAC · 1SVR740700R2200: Elume price today ₹8,683 per pc incl. GST, 53% below the ₹18,396 MRP. The price has held steady for the last 30 days.
The CM-MSS.23P belongs to the CM-MSS thermistor motor protection relay range. It operates with a rated control supply voltage of 110-130 V AC and 220-240 V AC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. It features one sensor circuit to monitor PTC temperature sensors and works according to the closed-circuit principle. The relay can be reset automatically, manually or remotely after the failure has been removed. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers maintenance free Easy Connect Technology with push-in terminals.
An on-delay timer switches its output after the set time once it receives power or a start signal, while an off-delay timer holds its output on for the set time after the signal is removed. Multifunction timers offer both and other modes such as cyclic and interval.
A dedicated star-delta timer has a built-in short dead time between star and delta changeover to prevent a short circuit across contactors. The star time is set to suit how fast the motor reaches near full speed, often a few seconds to around 15 seconds.
A phase monitoring relay detects phase loss, phase reversal (wrong sequence) and often phase unbalance or under/over voltage, and trips the contactor coil to protect three-phase motors. It is especially useful for pumps, compressors and lifts where wrong rotation or single phasing can cause damage.
A cyclic or programmable timer can switch a pump contactor on and off at set intervals, but for tank level control a level controller relay with probes or a float switch is more reliable. The pump also needs proper motor protection like an MPCB or overload relay.
Most modern timers and monitoring relays are DIN rail mounted (35mm), while some older or plug-in types use an 8-pin or 11-pin socket base. Check the mounting type and whether the base is included.