ABB OVR T2 3N 40-275s P TS QS Surge Protective Device · 2CTB815704R0800: Elume price today ₹22,738 per pc incl. GST, 53% below the ₹48,174 MRP. The price has held steady for the last 30 days.
Surge protective devices SPD type 2 protect low-voltage consumer systems against surge voltages as they are tested as SPD type 2 according to IEC 61643-11. The devices are compatible with the System pro M compact series. The SPD with "TS" are optionally equipped with a auxiliary contact. The variants with "reserve varistor" (s) offer additional protection for the system, as the SPD is not completely disconnected from the mains at the end of its service life, but with an additional smaller varistor still guarantees basic protection and the system thus until the surge arrester is replaced is still protected
For most homes and apartments, a Type 2 SPD in the main DB is the standard choice. Type 1 or combined Type 1+2 is used at the service entrance of independent houses in lightning-prone areas or buildings with external lightning protection (SPDs are covered by IS 16463 (Part 11), identical to IEC 61643-11).
Yes. An SPD diverts surge energy to earth, so it works only with a proper, low-resistance earth connection kept as short as possible. Without good earthing it gives little or no protection.
No. SPDs are designed for short transient surges from lightning and switching, not sustained overvoltage such as from a broken neutral or poor supply. For that, use a voltage protection relay, an over/under voltage protector or stabilisers for sensitive equipment.
Most SPDs have an indicator window that turns from green to red when the protective element has reached end of life. Pluggable SPDs allow replacing only the cartridge; check the indicator periodically and after major thunderstorms.
Yes, an SPD should have backup protection (MCB or fuse) as specified by the manufacturer, so a failed SPD can be safely disconnected without tripping the whole installation. The backup rating is usually listed in the SPD datasheet.
Imax is the maximum surge current it can discharge once, In is the nominal current it can handle repeatedly, and Up is the voltage protection level (the let-through voltage), where lower is better. For 230 V homes, a Type 2 SPD with Imax around 40kA and a maximum continuous operating voltage (Uc) of 275 V or more is commonly used.