Legrand RTX³ Thermal Overload Relay · 100 to 160 A · RTX³ 400 for CTX³ 400 · Differential type with screw terminals · Class 10 A · 416787: Elume price today ₹21,142 per pc incl. GST, 26% below the ₹28,570 MRP. The price has held steady for the last 30 days.
Thermal overload relay RTX³ 400 100-160A class 10A. 1NO + 1NC Auxiliary contact (0,75A / 240V AC-15)
Set it to the motor's full-load current from the nameplate, not higher. In a star-delta starter where the relay is in the phase winding circuit, it is set to about 0.58 times the full-load current.
Most overload relays are designed to mount directly on specific contactor sizes of the same brand and range. For other brands or sizes, a separate mounting kit or panel mounting is needed, so check the compatibility list.
Most modern thermal overload relays have differential (single phasing) sensitivity and trip faster when one phase is lost, which helps protect three-phase motors. For full phase failure and phase reversal protection, a phase monitoring relay is also recommended.
Trip class indicates the maximum time to trip from cold at 7.2 times the set current: class 10 trips within 10 seconds and class 20 within 20 seconds (IS/IEC 60947-4-1). Class 10 suits normal motors, while class 20 or 30 is used for heavy-starting loads like crushers and fans with large inertia.
In manual reset, someone must press the reset button after a trip, while auto reset lets the relay reset itself once it cools. Manual reset is generally safer, since the motor will not restart unexpectedly.