Siemens Sirius 3RT25 Power Contactor · 4P 2 NO + 2 NC · 18 A AC-1 · 110 V DC coil · S00 · 3RT2516-1BF40: Elume price today ₹5,569 per pc incl. GST, 40% below the ₹9,281 MRP. Today's price is the lowest of the last 30 days (high ₹9,281).
Siemens Sirius 3RT2 Power Contactor (article 3RT2516-1BF40) is a contactor from Siemens, sold by Elume with a GST invoice and pan-India delivery. Priced at the Siemens India list price of 2026 (MRP before GST Rs 7,865), GST included in the price shown.
Select by the contactor's AC-3 current (or kW) rating at your supply voltage, which should be at least the motor's full-load current from the nameplate. Do not go by the higher AC-1 rating, which applies only to resistive loads (contactors are covered by IS/IEC 60947-4-1).
AC-1 is for non-inductive or slightly inductive loads like heaters, while AC-3 is for starting and stopping squirrel cage motors. The same contactor has a much lower AC-3 rating than AC-1, and AC-4 (inching or plugging) is even more demanding.
No. A contactor only switches the motor on and off; overload protection needs a thermal overload relay and short-circuit protection needs an MPCB, MCB, MCCB or fuses upstream.
Common causes are low or fluctuating control voltage, a wrong coil voltage, dust or rust on the magnet faces, or a broken shading ring. Check the supply at the coil terminals first, then clean or replace the contactor if needed.
Most contactors have built-in auxiliary contacts (NO and/or NC) for holding and interlocking circuits, and many allow add-on auxiliary blocks on the front or side. Check the contact configuration and add-on compatibility in the product details.
A star-delta starter uses three contactors (main, delta and star), a star-delta timer and an overload relay. The main and delta contactors are typically sized at about 58% of the motor current and the star contactor smaller, as per the manufacturer's selection table.