Electrical BOM for a 3 kW, 5 kW and 10 kW Rooftop Solar System (DCDB, ACDB, Earthing)
- DCDB: one DC-rated MCB or fuse per string, a DC isolator if your specification asks for one, and a PV SPD. Every device must be rated above the cold-weather string Voc.
- ACDB: an AC MCB sized just above the inverter's maximum output current, a Type 2 AC SPD (1P+N or 3P+N), and an RCCB or isolator if your DISCOM requires it.
- 3 kW single-phase: one string, 20 A AC MCB. 5 kW: usually two strings, 32 A AC MCB. 10 kW three-phase: two strings, 800-1000 V DC devices, and a four-pole AC MCB with a 3P+N SPD.
- Earthing is usually specified as separate earth electrodes for the array/DC side, the AC side and the lightning arrester. Check your DISCOM's specification.
- Download our free 3, 5 and 10 kW BOM template and edit it for your module, inverter and DISCOM.
Modules and the inverter are the big-ticket items, and installers usually have a fixed supplier for both. The rest of the electrical balance of system (DCDB, ACDB, SPDs, cable, connectors and earthing) is where a quote turns into a dozen small purchases from three or four shops, and where most inspection observations come from.
This guide sets out a standard electrical BOM for the three sizes that make up most residential rooftop work in India, with the rating logic behind every line, so you can standardise your kits and buy them in sets. It assumes 540-550 W modules (Voc about 49-50 V, Isc about 13.9 A) and typical string inverters. Recalculate with your own datasheets and site low temperature before you buy. The free Excel version of this BOM includes a string-voltage calculator that does it for you.
3 kW single-phase: one string, one combo breaker set
Six 545-550 W modules in one string give about 300 V Voc at 25 C and about 310-320 V on a cold morning. DCDB: a 500 V DC MCB rated 20-25 A for the string, and a PV SPD. ACDB: a 20 A double-pole AC MCB (a 3 kW inverter delivers about 13 A) and a Type 2 1P+N AC SPD. L&K's Exora Solar Combo SC222025 combines a 20 A DP AC MCB with a 25 A DP 500 V DC MCB, which covers both breakers for this size in one purchase. Add DC solar cable (4 sq mm, typically 30-50 m of red and black combined depending on the roof), three to four pairs of MC4 connectors, AC cable from the inverter to the ACDB and meter, and earthing.
5 kW single-phase: two strings, 32 A on the AC side
Ten modules usually go in as two strings of five, one per MPPT, because a single string of ten can exceed 500 V on a cold morning. DCDB: one 500 V DC MCB per string (2 in total, 25 A each) and a PV SPD rated for the array voltage. ACDB: the 5 kW inverter delivers about 22 A, so a 32 A DP AC MCB, and a Type 2 1P+N AC SPD. L&K's SC223225 combo pairs a 32 A DP AC MCB with a 25 A DP 500 V DC MCB. Add one more DC-rated MCB for the second string. Check whether your DISCOM accepts a single-phase 5 kW connection. Some require three-phase above a certain sanctioned load.
10 kW three-phase: higher-voltage DC devices and 3P+N protection
A 10 kW system with about eighteen 550 W modules is usually wired as two strings of nine into a three-phase inverter, giving a cold Voc around 470 V per string. Longer strings on 1000 V inverters go higher. Use DC devices rated 800 V or 1000 V DC for margin. Legrand's DX3 Photovoltaic 800 V DC MCB, such as this 20 A unit, is one option, and the same range includes 600 V and 1000 V DC rotary isolators. ACDB: a four-pole AC MCB rated just above the inverter's maximum output current (about 14-15 A per phase at 10 kW, so typically 20-25 A, but check the datasheet), and a Type 2 3P+N AC SPD.
SPDs for every size: PV on the DC side, AC on the AC side
One PV SPD in the DCDB (Ucpv above the cold-weather Voc; this Havells unit is rated 1200 V DC, which covers all three sizes) and one AC SPD in the ACDB: 1P+N for single-phase inverters, 3P+N for three-phase. Type 2 is the normal class. Use Type 1+2 where the building has a lightning protection system the array cannot be separated from. Our solar SPD guide covers the choice in detail.
AC SPD and AC-side additions
The Havells Type 2 1P+N AC SPD (Uc 320 V, Imax 40 kA) is the standard ACDB surge protector for 3 kW and 5 kW single-phase systems, and the 3P+N version covers 10 kW three-phase. Some DISCOMs also require an RCCB or an AC isolator in the ACDB, and some inverters specify the type of RCD that may be used upstream. Check both the DISCOM specification and the inverter manual before you finalise the ACDB, because an inspection observation here means a second site visit.
Cable, connectors, enclosures and earthing: the lines we do not stock (yet)
To be clear about what Elume can and cannot supply today. DC solar cable (IS 17293 or EN 50618, rated 1.5 kV DC, typically 4 sq mm), MC4 connectors, IP65 DCDB and ACDB enclosures, earthing electrodes and lightning arresters are not on our shelf. Order them from your usual source, and we will quote them through a bulk enquiry where we can. Two technical points: use MC4 connectors from one manufacturer for both halves of each joint, because cross-mating different brands is a known cause of hot joints; and follow your DISCOM's earthing specification, which commonly asks for separate earth electrodes for the array and DC side, the AC side and the lightning arrester.
Buying tips
- Fix three standard kits (3, 5 and 10 kW) for your usual modules and inverters, and buy the switchgear for ten systems at a time. Wholesale pricing applies from 15 units of the same item.
- Recalculate cold-weather Voc for every new module model before you reuse a kit. A few volts more per module can push a string past 500 V.
- Keep a printed DCDB and ACDB layout in each kit so every crew wires polarity, SPD earthing and labelling the same way.
- Keep the DISCOM's latest technical specification and approved make list on file. They change, and inspections follow the current version.
- Ask for GST invoices with HSN codes for every line. PM Surya Ghar paperwork and your own input tax credit both need them.
Frequently asked questions
What components go in a solar DCDB?
A DC-rated MCB or fuse for each string (or a DC isolator), a PV surge protection device, and the enclosure with DC busbars or terminals. Every device must be rated above the string's cold-weather open-circuit voltage.
What components go in a solar ACDB?
An AC MCB sized for the inverter's maximum output current, a Type 2 AC SPD (1P+N or 3P+N), and an RCCB or isolator where the DISCOM requires it, in an enclosure suitable for the location.
What size MCB do I need for a 5 kW solar inverter?
A 5 kW single-phase inverter delivers about 22 A, so a 32 A double-pole AC MCB is typical. On the DC side, use a 500 V DC MCB of about 25 A per string, provided each string's cold Voc stays below 500 V.
How many earth pits does a rooftop solar system need?
Many DISCOM and MNRE-linked specifications ask for separate earthing for the array and DC side, the AC side, and the lightning arrester, often three electrodes. Follow your DISCOM's current specification.
Can Elume supply a full solar BOS kit?
We supply the switchgear and surge protection lines today (DC and AC MCBs, isolators, PV and AC SPDs, RCCBs) with GST invoices and wholesale pricing from 15 units. For cable, connectors and enclosures, send a bulk enquiry and we will quote what we can source.
Compare MRP vs the Elume price across brands, with wholesale prices on 15+ units.
Browse the catalogue →