Schneider Easy TeSys LRE Thermal Overload Relay · 0.63-1 A · LRE05LRE05↓ 40% off1 / 6
BrandSchneider
CategoryIndustrial Control
Specification0.63…1 A
Brand SKULRE05
AvailabilityIn stock · ships in 24h
Delivery8 to 15 business days after dispatch
Schneider· In stock
Visit the Schneider store

Schneider Easy TeSys LRE Thermal Overload Relay · 0.63-1 A · LRE05

Setting: 0.63…1 A
$38.60/pc-40%
$64.33
Wholesale · 15+ units
$36.67 /pc
Add to cart
Buy now
Delivery in 8 to 15 business days after dispatch
Buying in bulk? Ask our Export desk for a quote.
$38.60 /pc
Delivery in 8 to 15 business days
🏷️
100% genuine
Brand-authorised stock, sourced through authorised channels
🧾
Export invoice
Every international order ships with an export invoice for customs
🌍
Worldwide delivery
Dispatched from Ghaziabad, India · fee by weight, shown at checkout
📦
Wholesale built in
Wholesale price at 15+ units: $36.67/pc on this product, applied automatically

The LRE relay is a differential thermal overload relays for use with fuses or magnetic circuit-breakers GV2 L and GV3 L. Its thermal setting range is 0.63-1A 50/60Hz and the tripping class is 10A conforming to IEC 60947-4-1. It can be direct mounted on EasyPact TVS contactors with screw clamp terminals connection. It protects unbalanced loads and motors with 0.25kW at 400VAC. It provides manual or automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach).

As published by Schneider. Verify critical parameters against the datasheet before specifying.
Schneider Schneider Easy TeSys LRE Thermal Overload Relay · 0.63-1 A · LRE05 · LRE05
Ingress protectionIP20
Reference standardEN/IEC 60947-1
ColourGrey (RAL 7011)
Net weight0.13 kg
BrandSchneider
Brand SKULRE05
ELINEP3CMFR34K
Sold asPer pc
Depth70 mm
RangeEasy TeSys
Width45 mm
Height44.5 mm
StandardsEN/IEC 60947-1 · EN/IEC 60947-5-1 · EN/IEC 60947-4-1 · GB/T 14048.1 · GB/T 14048.4 · GB/T 14048.5 · EN/IEC 60335-1:Clause 30.2 · EN/IEC 60335-2-40:Annex JJ
Control typePush-button red stop: · Push-button green reset:
Network typeAC
Fire resistance850 °C conforming to IEC 60068-2-1
Local signallingTrip indicator
Mounting supportUnder contactor · Plate, with specific accessories · Rail, with specific accessories
Range of productEasy TeSys Protect
Device short nameLRE
Network frequency50...60 Hz
Relay applicationMotor protection
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Dielectric strength6 kV at 50 Hz conforming to IEC 60255-5
Signalling functionRelay trip indicator
Protective treatmentTH conforming to IEC 60068
Mechanical robustnessShocks: 6 Gn for 11 ms conforming to IEC 60068-2-7 · Vibrations: 3 GN conforming to IEC 60068-2-6
Product compatibilityLC1E06...38
Associated fuse rating4 A gG for power circuit · 2 A aM for power circuit · 5 A gG for signalling circuit
Product certificationsCB Scheme · CCC · CE · EAC
Thermal overload classClass 10A conforming to IEC 60947-4-1
Connections - terminalsPower circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: flexible without cable end · Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end · Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: solid without cable end · Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end · Signalling circui
IP degree of protectionIP20 conforming to IEC 60529
Temperature compensation-20…60 °C
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1
Product or component typeDifferential thermal overload relay
Auxiliary contact composition1 NO + 1 NC
Electromagnetic compatibilitySurge withstand: 6 kV conforming to IEC 60801-5
Recommended tightening torquePower circuit: 1.7 N.m - on screw clamp terminals · Signalling circuit: 1.7 N.m - on screw clamp terminals
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
[Ue] rated operational voltage<= 690 V AC
Ambient air temperature for storage-60…80 °C
Thermal protection adjustment range0.63…1 A
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1 · -20…70 °C with derating
[Uimp] rated impulse withstand voltage6 kV
[Ith] conventional free air thermal current5 A for signalling circuit
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.
What should I set the overload relay to?

Set it to the motor's full-load current from the nameplate, not higher. In a star-delta starter where the relay is in the phase winding circuit, it is set to about 0.58 times the full-load current.

Will this overload relay fit my contactor?

Most overload relays are designed to mount directly on specific contactor sizes of the same brand and range. For other brands or sizes, a separate mounting kit or panel mounting is needed, so check the compatibility list.

Does it protect against single phasing?

Most modern thermal overload relays have differential (single phasing) sensitivity and trip faster when one phase is lost, which helps protect three-phase motors. For full phase failure and phase reversal protection, a phase monitoring relay is also recommended.

What is trip class 10 and class 20?

Trip class indicates the maximum time to trip from cold at 7.2 times the set current: class 10 trips within 10 seconds and class 20 within 20 seconds (IS/IEC 60947-4-1). Class 10 suits normal motors, while class 20 or 30 is used for heavy-starting loads like crushers and fans with large inertia.

What is the difference between manual and auto reset?

In manual reset, someone must press the reset button after a trip, while auto reset lets the relay reset itself once it cools. Manual reset is generally safer, since the motor will not restart unexpectedly.