Schneider Schneider PowerLogic VPL12 Power Factor Controller · VarPlus Logic · VPL 12 · VPL12N · VPL12N
Ingress protectionFront face: IP41
Reference standardIEC 61000-6-4
Net weight0.6 kg
BrandSchneider
Brand SKUVPL12N
ELINEKJRC6DHMF
Sold asPer pc
Depth58 mm
RangePowerLogic
Width144 mm
Height144 mm
StandardsIEC 61000-6-4 · UL 61010-1 · EN 61010-1 · IEC 61000-6-2 · IEC 61326-1
Input typePhase to phase · Phase to neutral · Insensitive to CT polarity · Insensitive to phase rotation polarity · Current input CT...X/5 A and X/1 A
Colour codeFront: dark grey RAL 7016
Output typeControl relay: 0.2 A 110 V DC · Control relay: 1 A 48 V DC · Control relay: 2 A 400 V AC 50/60 Hz · Control relay: 1 A 24 V DC · Control relay: 5 A 250 V AC 50/60 Hz · Control relay: 5 A 120 V AC 50/60 Hz · Fan: 5 A 250 V AC 50/60 Hz · Fan: 1 A 48 V DC · Alarm relay: 5 A 250 V AC 50/60 Hz · Alarm relay: 1 A 48 V DC
Display size56 x 25 mm
Display typeBacklit LCD
Product namePowerLogic PFC Controller
Metering typePower factor and displacement PF (signed, four quadrant) · Total current harmonic distortion THD (I) · Power factor average over lifetime · Temperature maximum · Phase current I1, I2, I3 RMS on load · Active power P, P1, P2, P3 on load · Reactive power Q, Q1, Q2, Q3 on load · Apparent power S, S1, S2, S3 on load · Voltage U21, U32, U13, V1, V2, V3 on load
Mounting modeFlush-mounted
Data recording5 alarms
Input functionSwitch: 1 x dry contact
Operating modeManual or automatic
Type of alarmsStep power loss ( 6 A CT) / Action: message and alarm contact · Hunting (unstable regulation) / Action: message and alarm contact + step blocked · Low current ( 130 % I1) / Action: message and alarm contact + step switched off · Overtemperature (50 °C) / Action: message and alarm contact + step switched off · Overtemperature (30 °C) / Action: fan switch · Overvoltage (+/- 10 %) / Action: message a
Type of settingChoice of stepping programs: auto · Choice of stepping programs: LIFO · Choice of stepping programs: linear · Delay between 2 successive switch on the same step: 5...1200 s · Step configuration programming: auto · Step configuration programming: off · Step configuration programming: fixed · Target cos phi: 0.7 inductive...0.7 capacitive · Target cos phi: dual cos φ
Mounting supportPanel - thickness: 1…3 mm
Time delay range1...6500 s (on reconnection) · 1...6500 s (on response)
Device connectionCommunication protocol: Modbus interface: RS485
Device short nameVPL12
Mounting locationIn cabinet
Compatibility codeVPL 12
Cut-out dimensions138 x 138 mm
Function availableManual programming · Automatic initialisation · Automatic detection · Advanced programming (expert) · Any step sequence
Operating altitude<= 2000 m
Provided equipmentUser manual
Measurement current0…5 A
Measurement voltage90…550 V AC 50/60 Hz
Type of measurementCapacitor current overload Irms/I1 · Individual voltage harmonic · Power factor · Operating time · Cos φ · Ambient temperature inside the cubicle · Tan φ
Measurement accuracyVoltage +/- 1 % · Current +/- 1 % · Frequency +/- 1 % · Energy (P,Q,S) +/- 2 % · Cos φ +/- 2 % · Total voltage harmonic distortion THD (U) +/- 2 % · Individual voltage harmonic +/- 3 % · Temperature +/- 3 °C
Information displayedNumber of switching cycles per step · Individual step size in kVAr · Remaining step capacity in %
Product certificationsEAC · NRTL · cNRTL · CE
IP degree of protectionFront face: IP41 · Rear face: IP20
Operational Hours alarm100000 h without maintenance
Settings operating modeAutomatic · Manual
Operational counter alarm65000 cycles without maintenance
Product or component typePower factor controller
[Us] rated supply voltage90...550 V AC · <= 999 kV AC with external VT
Maximum at the common terminal10 A
Number of step output contacts12
Ambient air temperature for operation-20…60 °C
Number of quadrant operation for generator application4
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.