Schneider Schneider Harmony Control Relay · 3-phase · Phase loss sequence asymmetry and over/undervoltage · 183-528 V AC · RM10TE00 · RM10TE00
Ingress protectionIP20 (terminals)· IP30 (casing)
Reference standardIEC 60255-1
Net weight0.08 kg
BrandSchneider
Brand SKURM10TE00
ELINEJPFF6PDCD
Sold asPer pc
MarkingCE
Function3-phase phase loss sequence asymmetry and over/undervoltage
StandardsIEC 60255-1
Directives89/336/EEC - electromagnetic compatibility · 73/23/EEC - low voltage directive
Hysteresis2 %
Relay nameRM10TE
Relay typeMultifunction control relay
Reset time1500 ms time delay
Response time< 200 ms (in the event of a fault)
Measuring range183-528 V AC
Output contacts1 C/O
Time delay typeAdjustable 0.1...10 s, +/- 10 % of the full scale value
Pollution degree3 conforming to IEC 60664-1
Range of productHarmony Relay
Supply frequency50/60 Hz +/- 10 %
Measurement error< 0.05 %/°C with temperature variation · < 1 % over the whole range with voltage variation
Relative humidity95 % at 55 °C conforming to IEC 60068-2-30
Operating positionAny position without derating
Overvoltage categoryIII conforming to IEC 60664-1
Electrical durability100000 cycles
Insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5
Mechanical durability30000000 cycles
Supply voltage limits183…528 V AC
Product certificationsC-Tick · UL · GOST · CSA · GL
nominal output current5 A
Connections - terminalsScrew terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end · Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end · Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end · Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end
Dielectric test voltage2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
IP degree of protectionIP20 (terminals) conforming to IEC 60529 · IP30 (casing) conforming to IEC 60529
Maximum measuring cycle150 ms measurement cycle as true rms value
Power consumption in VA0…22 VA at 400 V AC 50 Hz
Switching capacity in VA1250 VA
Control circuit frequency50...60 Hz +/- 10 %
Maximum switching current5 A AC · 5 A DC
Maximum switching voltage250 V AC
Minimum switching current10 mA at 5 V DC
Phase failure sensitivity0.7 Un
Product or component typeModular measurement and control relays
Relay monitored parametersPhase sequence · Asymmetry · Undervoltage and overvoltage in window mode · Phase failure detection
Product specific applicationFor 3-phase supply
Threshold adjustment voltage2...20 % of Un selected · -2...-17 % in the range 220 V AC · +2...+10 % in the range 480 V AC · -2...-12 % in the range 208 V AC
Electromagnetic compatibilityEmission standard for industrial environments conforming to IEC 61000-6-4 · Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 · Immunity for industrial environments conforming to IEC 61000-6-2
[Ui] rated insulation voltage400 V conforming to IEC 60664-1
Control circuit voltage limits- 12 % + 10 % Un
Setting accuracy of time delay10 %
Adjustment of asymmetry threshold5...15 % of Un selected
Ambient air temperature for storage-40…70 °C · -40…70 °C
Ambient air temperature for operation-20…50 °C
Ratings as published by Schneider (se.com). Verify critical parameters against the datasheet before specifying.