TeSys GV motor circuit breaker, 3 poles (3P), 220A/690V, for protection of 3-phase motors 90-110kW@400V. It provides thermal magnetic protection and additional protections, breaking capacity Icu 70kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors). Thermal protection adjustable by dials with a setting current Ir in range 100-220A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In. Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
An MPCB has an adjustable overload setting matched to the motor's current and a magnetic trip set to handle motor starting current, plus phase loss sensitivity. An MCB has fixed overload settings meant for cables, so it does not protect a motor as precisely (MPCBs are covered by IS/IEC 60947-2 and 60947-4-1).
Yes, an MPCB gives short-circuit and overload protection plus isolation in one device, so with a contactor it forms a compact DOL starter without a separate overload relay or fuses. Check the manufacturer's coordination table for the right contactor pairing.
Yes, an MPCB can be used as a manual motor starter for occasional on/off switching. For frequent starts, remote control or float/pressure switch operation, pair it with a contactor.
Common accessories include auxiliary contacts, trip-indication contacts, undervoltage and shunt releases, enclosures for wall mounting and connection links to contactors. These are usually specific to the MPCB range.
Check that the dial is set to the motor's full-load current, that all three phases are present and balanced, and that the pump or load is not jammed. If the motor current is near the top of the range, the next range up may be needed; consult an electrician before increasing settings.